Plan Review Notes
Plan Review Notes For Permit 20041076
Permit Number 20041076
Review Stop G
Sequence Number 2
Notes
Date Text
2020-07-31 12:04:5407/31/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE GENERATOR ON THE ISOMETRIC IT SAYS 330 BTU'S AND
 ON YOUR SPECIFICATION IT HAS A 309 BTU'S PLEASE CHANGE
 A TALLY UP NEW TOTAL, PUT THE 309 ON THE ISO NOT 22 KW
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING GAS. A FULL EVALUATION OF ALL GAS EQUIPMENT
 WILL BE DONE AT FIELD, IF NOT TO CODE, IT MAY NEED TO
 BE BOUT UP TO CODE COMPLIANCE.
  
 3. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR PER THE 2017 FBC RES. SEC.
 G2420.4.
  
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.4.1.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2.
  
 6. NOTE: IF THE EXISTING SYSTEM IS LESS THAN A 2 PSI
 SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO 2 PSI, A
 LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE EXISTING
 APPLIANCES PER THE 2017 FBC RES. SECS. G2412.4,
 G2412.8, G2413.1, G2413.2, G2413.3.
  
 7. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
  
 8. PLEASE SHOW AND LABEL UNIONS IN FRONT OF REGULATOR
 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2.
  
 9. SHOW DRIP LEG AND LABEL ON EQUIPMENT INSTALLED PER
 THE 2017 FBC RES. SEC. G2419.2.
  
 10. PLEASE SHOW THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  