2020-11-03 16:41:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20040980 2417 SPRUCE AVE
  
 4TH REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, PROVIDE NOTE ON S1-2 "PLUMBING
 FIXTURES AND WATER HEATER SHOWN IN TEA PREP AREA ARE
 EXISTING. SEE CLOSED PERMIT 20030394" AND SHOW EXISTING
 ABOVE GROUND GREASE INTERCEPTOR IN THE SAME ROOM.
 PLEASE NOTE THAT PER FBC PL 1003.2, WASTES THAT DO NOT
 REQUIRE TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED
 INTO ANY INTERCEPTOR OR SEPARATOR.
  
 2.PER WPB FBC 107.2.1, PROVIDE NOTE ON S1-2 "SHOWER
 BATHROOM AND HALF BATH ARE EXISTING (SEE CLOSED PERMIT
 13090363/EXPIRED PERMIT 11050468)."
  
 3.PER WPB FBC 107.2.1, PROVIDE SANITARY RISER DIAGRAM
 FOR NEW THREE COMPARTMENT SINK AT THE KAVA BAR.
  
 4.PER WPB FBC 107.2.1, PROVIDE WATER RISER DIAGRAM FOR
 NEW THREE COMPARTMENT SINK AT THE KAVA BAR.
  
 5.PER WPB FBC 107.2.1, ON S1-2 FLOOR PLAN PROVIDE WATER
 AND SANITARY PIPE ROUTING TO EXISTING PIPING SYSTEMS
 FOR NEW THREE COMPARTMENT SINK AT THE KAVA BAR.
  
 6. AS PREVIOUSLY REQUESTED, PROVIDE DETAIL OF WATER
 HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING
 INCLUDING CW, HW, VALVES (INCLUDING VACUUM RELIEF VALVE
 IF APPLICABLE FBC PL 504.2) , THERMAL EXPANSION CONTROL
 DEVICE (INCLUDING SIZE), T&P DISCHARGE (INCLUDING
 TERMINATION) AND WATER HEATER PAN AND DRAIN (INCLUDING
 TERMINATION) PER WPB FPC 107.2.1; COMPLY WITH FBC PL
 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6,
 504.7, 504.7.1 AND 504.7.2. WATER HEATER SHALL CONFORM
 TO FBC EC TABLE C404.2
 PER THE GENERAL CONTRACTOR, THE WATER HEATER IS AN
 EXISTING ELECTRIC WATER HEATER RHEEM MODEL # 81SV30D-B
 240V/3500KW NON SIMULTANEOUS 30 GALLON STORAGE TYPE;
 SERIAL # 0497B25563 MANUFACTURED APRIL 1997. SHOW
 COMPLIANCE WITH FBC EC TABLE C404.2. PLEASE NOTE, THE
 SUBMITTED MANUFACTURER?S SPECIFICATION SHEETS DO NOT
 INCLUDE THIS WATER HEATER AS IT HAS APPARENTLY BEEN
 DISCONTINUED. IF THE WATER HEATER IS OUT OF COMPLIANCE,
 IT SHALL BE REPLACED.
  
 7.REGARDING THE NOTE ON S1-1 "DRINKING FOUNTAIN HAS
 BEEN ELIMINATED, SHOULD A CLIENT OR PATRON NEED A GLASS
 OF WATER, THEY MAY ASK THE BARTENDER FOR ONE", PLEASE
 BE ADVISED THAT FBC PL 410.4 STATES " WHERE RESTAURANTS
 PROVIDE DRINKING WATER IN A CONTAINER FREE OF CHARGE,
 DRINKING FOUNTAINS SHALL NOT BE REQUIRED IN THOSE
 RESTAURANTS"; THE NEW OCCUPANCY IS M-MERCANTILE. IN
 ORDER FOR THIS RULE TO BE APPLIED AN A2 OCCUPANCY WHICH
 INCLUDES RESTAURANTS, BARS, ETC., WOULD ALLOW THIS RULE
 TO BE USED. AT THIS TIME, A DRINKING FOUNTAIN
 (BI-LEVEL) IS STILL REQUIRED WITH AN ALCOVE TO COMPLY
 WITH FBC ACC 307.2.
  
 8.PROVIDE SPECIFICATION FOR PIPING MATERIAL AND HOT
 WATER INSULATION. PARTIALLY COMPLIED; STILL NEED PIPING
 MATERIAL.
  
 9.AGAIN: THE SHOWER IS NOT BEING USED. PER WPB FBC
 107.2.1, PROVIDE DETAILS ON DECOMMISSIONING OF THE
 UNIT, INCLUDING BUT NOT LIMITED TO CAPPING THE DRAIN TO
 PREVENT SEWER GAS FROM ENTERING THE BUILDING DUE TO
 TRAP EVAPORATION. TO BE CLEAR, PROVIDE NOTE ON THE
 PLAN. IT IS NOT ENOUGH TO NOTE ON RESPONSE LETTER AS
 THE INSPECTOR LOOKS AT THE PLANS WHEN MAKING
 INSPECTION.
 ADDITIONALLY, THERE IS STILL NO SIDE WALL INDICATED FOR
 THE WATER CLOSET AS REQUIRED BY FBC ACC 604.2. PER WPB
 FBC 107.2.1 PROVIDE ON THE PLANS THE REQUIRED SIDE
 WALL.
  
 10.AS NOTED IN THE LAST REVIEW,2017 FBC-B 1210.2.2.
 WALLS & PARTITIONS. THIS COMMENT IS A RESULT OF THE
 BUILDING OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY
 PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS REQUIRING
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE PER FBC 1210.2.2
 AND SPECIFICALLY NOTE THAT PAINT OR EPOXY IS NOT
 ACCEPTABLE.
  
 11. AGAIN: PER WPB FBC 107.2.1, SHOW HOW TEMPERED WATER
 IS SUPPLIED TO LAVATORIES. SHOW COMPLIANCE WITH FBC PL
 607.1 AND 416.5; ADDED COMMENT: DEVICES SHALL CONFORM
 TO ASSE 1070.
  
 12.THIS COMMENT HAS BEEN ACKNOWLEDGED IN THE RESPONSE
 LETTER: AS THIS PERMIT IS AFTER THE FACT, AT THE
 PLUMBING INSPECTOR'S DISCRETION, SHOW THAT ANY EXISTING
 PLUMBING INFRASTRUCTURE, INCLUSIVE OF PIPING, PLUMBING
 FIXTURES AND APPLIANCES SHOWN ON THE DEMOLITION PLAN,
 IS CODE COMPLIANT. THIS MAY REQUIRE PROVIDING
 DOCUMENTATION OF, OPENING OF WALLS AND FLOORS, PRESSURE
 TESTS, VIDEO CAM OF BURIED SANITARY, ETC., AS
 DETERMINED BY THE PLUMBING INSPECTOR. PLEASE CALL TIM
 LARGE AT 561-805-6692 FOR ADDITIONAL INFORMATION AND/OR
 CLARIFICATION
  
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE PREVIOUS REVIEW.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL FORM.
 PLEASE, ADDITIONALLY, INSERT CORRECTED PAGES INTO TO
 SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED
 SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  