2020-10-28 15:06:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20040980 2417 SPRUCE AVE
  
 3ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.NEW COMMENT: PER FBC ACC 307.2, OBJECTS WITH LEADING
 EDGES MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES
 ABOVE THE FINISH FLOOR OR GROUND SHALL PROTRUDE 4
 INCHES MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH.
 PROVIDE ALCOVE WALL FOR DRINKING FOUNTAIN TO ACHIEVE
 THIS.
  
 2. THE SUBMITTED FLOOR PLAN DOES NOT SHOW A DETAIL FOR
 THE RESTROOM/ BATHROOM FLOOR PLAN NOR ELEVATIONS FOR
 EACH OF THE ACCESSIBLE ELEMENTS IN THE BATHROOM. IN THE
 RESPONSE LETTER IT STATES NEW RESTROOM DETAILS. WHAT WE
 ARE LOOKING FOR IN RESTROOM DETAILS ARE DEDICATED
 DIMENSIONED FLOOR PLAN OF THE BATHROOM WITH CLEAR FLOOR
 SPACES, TURNING SPACE AND DOOR SWING AS WELL AS
 ELEVATION DETAILS FOR (4) WALLS OF THE RESTROOM WITH
 ALL FIXTURES DIMENSIONED, AND ALL ELEMENTS OF THE
 RESTROOM DIMENSIONED TO SHOW CODE COMPLIANCE INCLUDING
 VERBIAGE SUCH AS IN THE CASE OF GRAB BARS " TOP OF THE
 GRIPPING SURFACE" OR IN THE CASE OF MIRRORS "THE BOTTOM
 EDGE OF THE REFLECTING SURFACE". SEE BELOW.
 THIRD REQUEST: PER WPB FBC 107.2.1, TO SHOW COMPLIANCE
 WITH FBC ACC CHAPTERS 3 AND 6 PROVIDE DETAILS (TO BE
 CLEAR PROVIDE PLAN VIEW AND ELEVATION VIEW, SEE
 BUILDING PLAN REVIEW COMMENT; THE SUBMITTED FLOOR PLAN
 DOES NOT SHOW A DETAIL FOR THE RESTROOM/ BATHROOM FLOOR
 PLAN NOR ELEVATIONS FOR EACH OF THE ACCESSIBLE ELEMENTS
 IN THE BATHROOM.) INDICATING THE FOLLOWING:
 A. SHOWER SHALL COMPLY WITH REQUIREMENTS OF FBC ACC
 SECTION 608. N/A; SHOWER IS NOT USED. HOWEVER, A SIDE
 WALL SHALL BE IN PLACE FOR THE WATER CLOSET TO COMPLY
 WITH FBC ACC 604.2.
 B. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 C. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1. IT IS NOTED THAT A DETAIL IS
 SHOWN ON THE SUBMITTED PLAN BUT IS NOT IDENTIFIED. IT
 IS UNCLEAR AS TO WHAT KIND OF INFORMATION TWO OF THE
 DETAILS ARE TRYING TO PROVIDE.
 D. SHOW TURNING SPACE FOR WATER CLOSET(S) COMPLYING
 WITH FBC ACC 304.3.1 OR 304.3.2. PROVIDED, CLARIFY IN
 PLAN VIEW DETAIL.
 E. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 F. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 G. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 H. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 I. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE PER FBC ACC 609.4
 J. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 K. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 L. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES AND
 SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER LAVATORIES AND SINKS PER FBC
 ACC 606.5.
 M. PER FBC ACC 212.3, WHERE SINKS ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE
 PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY
 WITH 606.
 EXCEPTION: MOP OR SERVICE SINKS SHALL NOT BE REQUIRED
 TO COMPLY WITH 212.3.
 N. LAVATORIES AND SINKS SHALL HAVE A CLEAR FLOOR OR
 GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED PER FBC
 ACC 602.2.
 O. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 P. PER FBC ACC 602.1, DRINKING FOUNTAINS SHALL COMPLY
 WITH 307 AND 602.
 Q. PER FBC ACC 602.2, DRINKING FOUNTAINS SHALL HAVE A
 CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR A FORWARD APPROACH AND CENTERED ON THE
 UNIT. KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL
 BE PROVIDED.
 R. PER FBC ACC 602.3, OPERABLE PARTS FOR THE DRINKING
 FOUNTAIN SHALL COMPLY WITH 309.
 S. PER FBC ACC 602.4, SPOUT OUTLET FOR THE DRINKING
 FOUNTAIN SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
 T. PER FBC ACC 602.5, THE SPOUT FOR THE DRINKING
 FOUNTAIN SHALL BE LOCATED 15 INCHES (380 MM) MINIMUM
 FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM) MAXIMUM
 FROM THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS.
 U. PER FBC ACC 602.7, SPOUT OUTLETS OF DRINKING
 FOUNTAINS FOR STANDING PERSONS SHALL BE 38 INCHES (965
 MM) MINIMUM AND 43 INCHES (1090 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 3. SECOND REQUEST: PER WPB FBC 107.2.1, SHOW HOW HOT
 WATER AS REQUIRED BY FBC PL SECTION 607 IS PROVIDED.
  
 4. THIRD REQUEST: PER WPB FBC 107.2.1, SHOW HOW
 TEMPERED WATER IS SUPPLIED TO LAVATORIES. SHOW
 COMPLIANCE WITH FBC PL 607.1 AND 416.5; ADDED COMMENT:
 DEVICES SHALL CONFORM TO ASSE 1070.
  
 AS THIS IS A CHANGE OF OCCUPANCY, THE FACILITY IS
 REQUIRED TO COMPLY WITH THE 2017 FLORIDA BUILDING CODES
 AS APPLICABLE TO THE DIFFERENT DISCIPLINES/TRADES.
 1.A REVIEW OF CITY RECORDS INDICATE THE SHOWER BATHROOM
 AND HALF BATH ARE EXISTING (SEE CLOSED PERMIT
 13090363/EXPIRED PERMIT 11050468); THE SINK IN THE
 KITCHEN AND THE SINK IN THE KAVA BAR ARE NEW, AS IS THE
 RANGE (NOW ELIMINATED) IN THE KITCHEN. ADDITIONALLY IT
 IS DISCOVERED THAT IN ADDITION TO THE THREE-COMPARTMENT
 SINK IN THE KITCHEN SPACE, THERE ARE TWO OTHER SINKS
 AND AN ABOVE GROUND GREASE INTERCEPTOR. (SEE CLOSED
 PERMIT 20030394). PER WPB FBC 107.2.1, SHOW ALL
 EXISTING FIXTURES. IF THEY ARE TO BE REMOVED, INDICATE
 THAT AND PROVIDE DIRECTION FOR SAFEING OF EXISTING
 PLUMBING SUPPLY LINES AND WASTE OUTLETS.
 A.PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE A
 PLUMBING PLAN(S) SHOWING THE FOLLOWING:
 1)PLAN VIEW AND SIZED RISER DIAGRAMS OF WATER SUPPLY
 AND SANITARY PIPING. IDENTIFY EXISTING AND NEW WITH
 POINTS OF CONNECTION TO THE EXISTING SYSTEMS. INCLUDE
 WATER HEATER, VALVES, BACKFLOW PREVENTERS AND OTHER
 PLUMBING APPURTENANCES AS APPLICABLE.
 2)IT IS ADVISABLE TO PROVIDE ONE OR MORE DEDICATED
 PLUMBING PLAN(S) TO PROVIDE THE REQUIRED INFORMATION IN
 A COMPREHENSIVE MANNER.
 3)COMMENT: PLAN VIEW DOES NOT SHOW WATER AND SANITARY
 PIPING AS REQUESTED. SECOND REQUEST; PROVIDE AND
 IDENTIFY EXISTING AND NEW WITH POINTS OF CONNECTION TO
 THE EXISTING SYSTEMS. INCLUDE WATER HEATER, VALVES,
 BACKFLOW PREVENTERS AND OTHER PLUMBING APPURTENANCES AS
 APPLICABLE.
 4)REGARDING THE ISOMETRIC, IT IS NOTED FOR WATER
 ALTHOUGH IT DOES SEEM TO INDICATE SANITARY. PLEASE NOTE
 A)THE DIAGRAM IS SCHEMATIC AND DOES NOT PROVIDE A
 COMPREHENSIVE LAYOUT THAT AN ISOMETRIC DRAWING DOES.
 B)THE PIPING TO THE EXISTING SINK IN THE "KITCHEN"
 SPACE IS NOT SHOWN.
 C)THE SANITARY PIPING ENDS AT THE FLOOR. SHOW NEW AND
 EXISTING PIPING. INDICATE POINTS OF CONNECTION OF NEW
 TO EXISTING.
 D)THE DRINKING FOUNTAIN DRAIN SHALL NOT CONNECT TO THE
 WET VENT, RATHER, SHALL CONNECT DOWNSTREAM OF THE WATER
 CLOSET PER FBC PL 912.1 AND SHALL BE TRAPPED PER FBC PL
 1002.1 AND INDIVIDUALLY VENTED PER FBC PL 910.1.
 E)ALL FIXTURES SHALL BE VENTED IN ACCORDANCE WITH FBC
 PL CHAPTER 9.
 F)ALL PIPING SHALL BE SIZED.
  
  
 5.SECOND REQUEST: PROVIDE A PLUMBING FIXTURE SCHEDULE
 SHOWING COMPLIANCE WITH FBC PL TABLE 403.1.
 SCHEDULE SHALL IDENTIFY EACH EXISTING AND NEW PLUMBING
 FIXTURE WITH DESCRIPTION; FOR EXAMPLE SK-1; THREE
 COMPARTMENT SINK/GLASSWASH OR SK-2; SERVICE SINK. BE
 SURE TO PROVIDE INFORMATION ON THE SINK IN THE AREA
 WHICH AT THIS TIME IS INDICATED KITCHEN.
  
 6.SECOND REQUEST: PROVIDE MINIMUM FIXTURE REQUIREMENTS
 COMPLYING WITH FBC PL TABLES 709.1 AND 604.4. PLEASE
 LOOK AT THE TABLES FOR REFERENCE
 A.FBC PL TABLE 709.1: FIXTURE UNIT LOAD AND TRAP SIZE
 FOR EXAMPLE, COMBINATION SINK AND TRAY (PLEASE NOTE,
 THREE COMPARTMENT SINK IS COVERED UNDER THIS IN FBC PL
 CHAPTER 2 DEFINITIONS; COMBINATION FIXTURE) 2 FIXTURE
 UNITS, 1-1/2 INCH TRAP SIZE.
 B.FBC PL TABLE 604.4: MAXIMUM FLOW RATE; FOR EXAMPLE, A
 SINK FAUCET IS 2.2GPM AT 60 PSI / QUANTITY; FOR
 EXAMPLE, A WATER CLOSET IS 1.6 GALLONS PER FLUSH
  
 7.PROVIDE WATER HEATER AND PROVIDE MANUFACTURER'S
 SPECIFICATION. INCLUDE ELECTRICAL CHARACTERISTICS OR
 FUEL GAS REQUIREMENTS AS APPLICABLE. PROVIDE DETAIL OF
 WATER HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING
 INCLUDING CW, HW, VALVES (INCLUDING VACUUM RELIEF VALVE
 IF APPLICABLE FBC PL 504.2) , THERMAL EXPANSION CONTROL
 DEVICE (INCLUDING SIZE), T&P DISCHARGE (INCLUDING
 TERMINATION) AND WATER HEATER PAN AND DRAIN (INCLUDING
 TERMINATION) PER WPB FPC 107.2.1; COMPLY WITH FBC PL
 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6,
 504.7, 504.7.1 AND 504.7.2. WATER HEATER SHALL CONFORM
 TO FBC EC TABLE C404.2
 A.SECOND REQUEST: PROVIDE DETAIL OF WATER HEATER
 SHOWING HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW,
 HW, VALVES (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE
 FBC PL 504.2) , THERMAL EXPANSION CONTROL DEVICE
 (INCLUDING SIZE), T&P DISCHARGE (INCLUDING TERMINATION)
 AND WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION)
 PER WPB FPC 107.2.1; COMPLY WITH FBC PL 607.3, 503.1,
 504.1, 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND
 504.7.2. WATER HEATER SHALL CONFORM TO FBC EC TABLE
 C404.2
 B.NEW COMMENT: PER THE GENERAL CONTRACTOR, THE WATER
 HEATER IS AN EXISTING ELECTRIC WATER HEATER RHEEM MODEL
 # 81SV30D-B 240V/3500KW NON SIMULTANEOUS 30 GALLON
 STORAGE TYPE; SERIAL # 0497B25563 MANUFACTURED APRIL
 1997. SHOW COMPLIANCE WITH FBC EC TABLE C404.2. PLEASE
 NOTE, THE SUBMITTED MANUFACTURER?S SPECIFICATION SHEETS
 DO NOT INCLUDE THIS WATER HEATER AS IT HAS APPARENTLY
 BEEN DISCONTINUED. IF THE WATER HEATER IS OUT OF
 COMPLIANCE, IT SHALL BE REPLACED.
  
 7.THIS COMMENT HAS BEEN ACKNOWLEDGED IN THE RESPONSE
 LETTER: AS THIS PERMIT IS AFTER THE FACT, AT THE
 PLUMBING INSPECTOR'S DISCRETION, SHOW THAT ANY EXISTING
 PLUMBING INFRASTRUCTURE, INCLUSIVE OF PIPING, PLUMBING
 FIXTURES AND APPLIANCES SHOWN ON THE DEMOLITION PLAN,
 IS CODE COMPLIANT. THIS MAY REQUIRE PROVIDING
 DOCUMENTATION OF, OPENING OF WALLS AND FLOORS, PRESSURE
 TESTS, VIDEO CAM OF BURIED SANITARY, ETC., AS
 DETERMINED BY THE PLUMBING INSPECTOR. PLEASE CALL TIM
 LARGE AT 561-805-6692 FOR ADDITIONAL INFORMATION AND/OR
 CLARIFICATION
  
 8.SECOND REQUEST: PROVIDE SPECIFICATION FOR PIPING
 MATERIAL AND HOT WATER INSULATION.
  
 9.ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 10.A COMMERCIAL KITCHEN AS DESIGNATED IN A2 OCCUPANCY
 IS STILL SHOWN. IF THERE IS NO KITCHEN THEN ELIMINATE
 REFERENCE TO KITCHEN AND PROVIDE NEW DESCRIPTION OF THE
 SPACE.
  
 11.PER WPB FBC 107.2.1, SHOW THE LOCATION AND SIZE OF
 THE EXISTING LEAD FREE RPZ BFP AND PROVIDE UP TO DATE
 CERTIFICATION OF THE SAME OR PROVIDE LOCATION, DETAIL
 AND SPECIFICATION FOR A NEW LEAD FREE RPZ BFP. BACKFLOW
 PREVENTER SHALL CONFORM TO WPB CROSS CONNECTION CONTROL
 MANUAL. PLEASE NOTE THAT AN EXISTING RPZ BFP IS NOW
 INDICATED ON THE PLANS. UP TO DATE CERTIFICATION OF
 DEVICE IS REQUIRED FOR FINAL INSPECTION.
  
 12.SECOND REQUEST: THE SHOWER IS NOT BEING USED. PER
 WPB FBC 107.2.1, PROVIDE DETAILS ON DECOMMISSIONING OF
 THE UNIT, INCLUDING BUT NOT LIMITED TO CAPPING THE
 DRAIN TO PREVENT SEWER GAS FROM ENTERING THE BUILDING
 DUE TO TRAP EVAPORATION.
 NO PROVISIONS NOTED ON NEW PLAN S1.2 AS INDICATED IN
 RESPONSE LETTER. ADDITIONALLY, THERE IS STILL NO SIDE
 WALL INDICATED FOR THE WATER CLOSET AS REQUIRED BY FBC
 ACC 604.2.
  
 13.NEW COMMENT. 2017 FBC-B 1210.2.2. WALLS &
 PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO
 LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE PREVIOUS REVIEW.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL FORM.
 PLEASE, ADDITIONALLY, INSERT CORRECTED PAGES INTO TO
 SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED
 SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  