2020-09-22 16:00:16 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20040980 2417 SPRUCE AVE |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| |
| 1. SECOND REQUEST: PER FBC PL 403.1 IN ACCORDANCE WITH |
| TABLE 403.1; OCCUPANCY MERCANTILE, PROVIDE A SERVICE |
| SINK. |
| |
| 2. SECOND REQUEST: PER FBC PL 403.1 IN ACCORDANCE WITH |
| TABLE 403.1; OCCUPANCY MERCANTILE, PROVIDE A DRINKING |
| FOUNTAIN. WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT |
| FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE |
| REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE |
| DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS |
| FOR STANDING PERSONS. A SINGLE DRINKING FOUNTAIN WITH |
| TWO SEPARATE SPOUTS THAT COMPLIES WITH THE REQUIREMENTS |
| FOR PEOPLE WHO USE A WHEELCHAIR AND STANDING PERSONS |
| SHALL BE PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE |
| DRINKING FOUNTAINS. |
| |
| 3. SECOND REQUEST: PER WPB FBC 107.2.1, TO SHOW |
| COMPLIANCE WITH FBC ACC CHAPTERS 3 AND 6 PROVIDE |
| DETAILS (TO BE CLEAR PROVIDE PLAN VIEW AND ELEVATION |
| VIEW, SEE BUILDING PLAN REVIEW COMMENT; THE SUBMITTED |
| FLOOR PLAN DOES NOT SHOW A DETAIL FOR THE RESTROOM/ |
| BATHROOM FLOOR PLAN NOR ELEVATIONS FOR EACH OF THE |
| ACCESSIBLE ELEMENTS IN THE BATHROOM.) INDICATING THE |
| FOLLOWING: |
| A. SHOWER SHALL COMPLY WITH REQUIREMENTS OF FBC ACC |
| SECTION 608. N/A; SHOWER IS NOT USED. HOWEVER, A SIDE |
| WALL SHALL BE IN PLACE FOR THE WATER CLOSET TO COMPLY |
| WITH FBC ACC 604.2. |
| B. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 |
| INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC |
| ACC 604.2 |
| C. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| WALL PER FBC ACC 604.3.1. IT IS NOTED THAT A DETAIL IS |
| SHOWN ON THE SUBMITTED PLAN BUT IS NOT IDENTIFIED. IT |
| IS UNCLEAR AS TO WHAT KIND OF INFORMATION TWO OF THE |
| DETAILS ARE TRYING TO PROVIDE. |
| D. SHOW TURNING SPACE FOR WATER CLOSET(S) COMPLYING |
| WITH FBC ACC 304.3.1 OR 304.3.2. PROVIDED, CLARIFY IN |
| PLAN VIEW DETAIL. |
| E. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER |
| FBC ACC 604.4. |
| F. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| WALL PER FBC ACC 604.5.1 |
| G. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 |
| H. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. |
| HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. |
| FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE |
| WATER CLOSET PER FBC ACC 604.6 |
| I. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 |
| MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP |
| OF THE GRIPPING SURFACE PER FBC ACC 609.4 |
| J. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC |
| ACC 604.8. |
| K. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE |
| FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 |
| INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS |
| REQUIRED BY FBC ACC 306.2 AND 306.3 |
| L. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES AND |
| SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR |
| ABRASIVE SURFACES UNDER LAVATORIES AND SINKS PER FBC |
| ACC 606.5. |
| M. PER FBC ACC 212.3, WHERE SINKS ARE PROVIDED, AT |
| LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE |
| PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY |
| WITH 606. |
| EXCEPTION: MOP OR SERVICE SINKS SHALL NOT BE REQUIRED |
| TO COMPLY WITH 212.3. |
| N. LAVATORIES AND SINKS SHALL HAVE A CLEAR FLOOR OR |
| GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A |
| FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE |
| CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED PER FBC |
| ACC 602.2. |
| O. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE |
| THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 |
| MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| ACC 603.3. |
| P. PER FBC ACC 602.1, DRINKING FOUNTAINS SHALL COMPLY |
| WITH 307 AND 602. |
| Q. PER FBC ACC 602.2, DRINKING FOUNTAINS SHALL HAVE A |
| CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 |
| POSITIONED FOR A FORWARD APPROACH AND CENTERED ON THE |
| UNIT. KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL |
| BE PROVIDED. |
| R. PER FBC ACC 602.3, OPERABLE PARTS FOR THE DRINKING |
| FOUNTAIN SHALL COMPLY WITH 309. |
| S. PER FBC ACC 602.4, SPOUT OUTLET FOR THE DRINKING |
| FOUNTAIN SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE THE |
| FINISH FLOOR OR GROUND. |
| T. PER FBC ACC 602.5, THE SPOUT FOR THE DRINKING |
| FOUNTAIN SHALL BE LOCATED 15 INCHES (380 MM) MINIMUM |
| FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM) MAXIMUM |
| FROM THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS. |
| U. PER FBC ACC 602.7, SPOUT OUTLETS OF DRINKING |
| FOUNTAINS FOR STANDING PERSONS SHALL BE 38 INCHES (965 |
| MM) MINIMUM AND 43 INCHES (1090 MM) MAXIMUM ABOVE THE |
| FINISH FLOOR OR GROUND. |
| |
| 5. SECOND REQUEST: PER WPB FBC 107.2.1, SHOW HOW HOT |
| WATER AS REQUIRED BY FBC PL SECTION 607 IS PROVIDED. |
| |
| 6. SECOND REQUEST: PER WPB FBC 107.2.1, SHOW HOW |
| TEMPERED WATER IS SUPPLIED TO LAVATORIES. SHOW |
| COMPLIANCE WITH FBC PL 607.1 AND 416.5. |
| |
| |
| 7. SECOND REQUEST: THE SUBMITTED BUILDING PERMIT |
| VALUATION APPEARS TO BE UNDER EVALUATED. PER WPB FBC |
| 109.3, PROVIDE VALUATION REFERENCES SUCH AS THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES SUCH AS MARSHALL-SWIFT, MEANS, ETC. VALUATION |
| SHALL BE THE TOTAL STRUCTURAL, ELECTRICAL, PLUMBING, |
| MECHANICAL, INTERIOR FINISHES, NORMAL SITE WORK, |
| ARCHITECTURAL AND DESIGN FEES, MARKET COST, OVERHEAD |
| AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| |
| NEW COMMENTS. |
| NO TRANSMITTAL LETTER WAS SUBMITTED. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| AS THIS IS A CHANGE OF OCCUPANCY, THE FACILITY IS |
| REQUIRED TO COMPLY WITH THE 2017 FLORIDA BUILDING CODES |
| AS APPLICABLE TO THE DIFFERENT DISCIPLINES/TRADES. |
| |
| 1.A REVIEW OF CITY RECORDS INDICATE THE SHOWER BATHROOM |
| AND HALF BATH ARE EXISTING (SEE CLOSED PERMIT |
| 13090363/EXPIRED PERMIT 11050468); THE SINK IN THE |
| KITCHEN AND THE SINK IN THE KAVA BAR ARE NEW, AS IS THE |
| RANGE IN THE KITCHEN. PER WPB FBC 107.2.1 AND |
| 107.3.5.1.3, PROVIDE A PLUMBING PLAN(S) SHOWING THE |
| FOLLOWING: |
| |
| 2.PLAN VIEW AND SIZED RISER DIAGRAMS OF WATER SUPPLY |
| AND SANITARY PIPING. IDENTIFY EXISTING AND NEW WITH |
| POINTS OF CONNECTION TO THE EXISTING SYSTEMS. INCLUDE |
| WATER HEATER, VALVES, BACKFLOW PREVENTERS AND OTHER |
| PLUMBING APPURTENANCES AS APPLICABLE. |
| |
| 3.PROVIDE A PLUMBING FIXTURE SCHEDULE SHOWING |
| COMPLIANCE WITH FBC PL TABLE 403.1. |
| |
| 4.PROVIDE MINIMUM FIXTURE REQUIREMENTS COMPLYING WITH |
| FBC PL TABLES 709.1 AND 604.4. |
| |
| 5.PROVIDE WATER HEATER AND PROVIDE MANUFACTURER?S |
| SPECIFICATION. INCLUDE ELECTRICAL CHARACTERISTICS OR |
| FUEL GAS REQUIREMENTS AS APPLICABLE. PROVIDE DETAIL OF |
| WATER HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING |
| INCLUDING CW, HW, VALVES (INCLUDING VACUUM RELIEF VALVE |
| IF APPLICABLE FBC PL 504.2) , THERMAL EXPANSION CONTROL |
| DEVICE (INCLUDING SIZE), T&P DISCHARGE (INCLUDING |
| TERMINATION) AND WATER HEATER PAN AND DRAIN (INCLUDING |
| TERMINATION) PER WPB FPC 107.2.1; COMPLY WITH FBC PL |
| 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6, |
| 504.7, 504.7.1 AND 504.7.2. WATER HEATER SHALL CONFORM |
| TO FBC EC TABLE C404.2 |
| |
| 6.AS THIS PERMIT IS AFTER THE FACT, AT THE PLUMBING |
| INSPECTOR'S DISCRETION, SHOW THAT ANY EXISTING PLUMBING |
| INFRASTRUCTURE, INCLUSIVE OF PIPING, PLUMBING FIXTURES |
| AND APPLIANCES SHOWN ON THE DEMOLITION PLAN, IS CODE |
| COMPLIANT. THIS MAY REQUIRE PROVIDING DOCUMENTATION OF, |
| OPENING OF WALLS AND FLOORS, PRESSURE TESTS, VIDEO CAM |
| OF BURIED SANITARY, ETC., AS DETERMINED BY THE PLUMBING |
| INSPECTOR. PLEASE CALL TIM LARGE AT 561-805-6692 FOR |
| ADDITIONAL INFORMATION AND/OR CLARIFICATION |
| |
| 7.PROVIDE SPECIFICATION FOR PIPING MATERIAL AND HOT |
| WATER INSULATION. |
| |
| 8.ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| SECTION 107.3.5). |
| |
| 9.A COMMERCIAL KITCHEN AS DESIGNATED IN A2 OCCUPANCY IS |
| SHOWN. |
| A.PER FBC PL 1003.3.1, A GREASE INTERCEPTOR OR |
| AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO |
| RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH |
| GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS, |
| SUCH AS IN RESTAURANTS, HOTEL KITCHENS, HOSPITALS, |
| SCHOOL KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS. |
| FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS, |
| PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK |
| STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE |
| DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS |
| WITHOUT PRERINSE SINKS. GREASE INTERCEPTORS AND |
| AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE WASTE |
| ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS, OILS |
| OR GREASE TO BE DISCHARGED. WHERE LACK OF SPACE OR |
| OTHER CONSTRAINTS PREVENT THE INSTALLATION OR |
| REPLACEMENT OF A GREASE INTERCEPTOR, ONE OR MORE GREASE |
| INTERCEPTORS SHALL BE PERMITTED TO BE INSTALLED ON OR |
| ABOVE THE FLOOR AND UPSTREAM OF AN EXISTING GREASE |
| INTERCEPTOR. |
| B.PER FAC 64E-11.003(5)(D), AT LEAST ONE EMPLOYEE |
| HANDWASHING FACILITY MUST BE LOCATED WITHIN EACH FOOD |
| PREPARATION AREA, WITHIN 20 FEET OF THE DUTY STATION, |
| VISIBLE AND ACCESSIBLE THROUGH AN UNOBSTRUCTED AREA. |
| |
| 10.PER WPB FBC 107.2.1, SHOW THE LOCATION AND SIZE OF |
| THE EXISTING LEAD FREE RPZ BFP AND PROVIDE UP TO DATE |
| CERTIFICATION OF THE SAME OR PROVIDE LOCATION, DETAIL |
| AND SPECIFICATION FOR A NEW LEAD FREE RPZ BFP. BACKFLOW |
| PREVENTER SHALL CONFORM TO WPB CROSS CONNECTION CONTROL |
| MANUAL. |
| |
| 11.REGARDING THE RANGE IN THE KITCHEN: PER WPB FBC |
| 107.2.1, CLARIFY IF IT IS ELECTRIC OR GAS FIRED. |
| |
| 12.THE SHOWER IS NOT BEING USED. PER WPB FBC 107.2.1, |
| PROVIDE DETAILS ON DECOMMISSIONING OF THE UNIT, |
| INCLUDING BUT NOT LIMITED TO CAPPING THE DRAIN TO |
| PREVENT SEWER GAS FROM ENTERING THE BUILDING DUE TO |
| TRAP EVAPORATION. |
| |
| 13.PER WPB FBC 107.2.1, SUBMIT A SLAB REPAIR DETAIL FOR |
| REVIEW AND ONCE APPROVED HAVE TWO COPIES AT THE JOB |
| SITE. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM |
| THICKNESS OF THE CONCRETE TO BE REPLACED, AND THE PSI |
| OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF THE |
| DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE EXISTING |
| SLAB, THE ANCHORING MATERIAL FOR THE DOWELS AND THE |
| SPACING OF THE DOWELS ON CENTER. THE REPAIR SHALL ALSO |
| INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED |
| VAPOR BARRIER OVER WELL-COMPACTED SOIL. A COPY OF THE |
| TERMITE CERTIFICATE SHALL BE ONSITE FOR A FINAL |
| INSPECTION. |
| |
| A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS |
| FROM THE PREVIOUS REVIEW. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING |
| EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL FORM. |
| PLEASE, ADDITIONALLY, INSERT CORRECTED PAGES INTO TO |
| SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED |
| SHEETS. |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |
| |
| |