Plan Review Notes
Plan Review Notes For Permit 20040980
Permit Number 20040980
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2020-09-21 15:16:46THERE WERE SEVERAL COMMENTS THANK WERE NOT ADDRESSED
 ABD ARE RESUBMITTED BELOW:
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 2) THERE ARE NO INDICATIONS OF EXIT SIGNS
  
 PLEASE PROVIDE.
  
  
 3) THERE ARE NO INDICATIONS OF DOOR HARDWARE/ LOCKS ON
 THE DOORS.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
  
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE PROIDE DETAILS IN COMPLIANCE
  
  
  
 4) THERE ARE NO DETAILS REGARDING THE CABINET
 STRUCTURE.
  
 PLEASE PROVIDE HEIGHT/WIDTH, DOORS, ETC AND THE PURPOSE
 THIS STRUCTURE SERVES.
  
  
  
 5) THERE APPEARS TO BE STOVE LOCATED IN THE REAR AREA.
 PLEASE CONFIRM AND WHAT IT'S PURPOSE IS AND ITS HOOD
 AND FIRE SUPRESSION SYSTEM.
  
 RESIDENTIAL STOVES SHOULD NOT BE LOCATED IN CERTAIN
 OCCUPANCIES, BASED ON HOW THEY ARE USED AND HOW THEY
 ARE PROTECTED.
  
 PLEASE PROVIDE DETAILS OR REMOVE.
  
  
  
 NEW COMMENT:
  
 1) THE EXIT FROM THE KITCHEN GOES THROUGH THE STORAGE
 AREA.
  
 PER NFPA 101 , CH 7 MEANS OF EGRESS
  
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS,
 STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND
 37,
 RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR
 OTHER ROOMS OR
 SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH
 ROOMS OR
 SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18,
 19, 22, OR 23.
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE
 THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS,
 PROVIDED THAT SUCH
 ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED.
 FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE
 ARRANGED SO
 THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA
 IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
  
 THE KITCHEN EXIT CAN PASS THROUGH TO THE FRONT DOOR.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]