2020-06-16 13:24:41 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20040979 |
| |
| CODES IN EFFECT: |
| |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE SPECS SHEETS AND CALCULATIONS FOR |
| HEATING AND COOLING EQUIPMENT SIZING FOR THIS ADDITION. |
| FBC EC M403.7; FBC EC 101.5.1.1.2 |
| |
| 2) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE |
| MECHANICAL SYSTEM FOR THIS ADDITION. |
| |
| 3) PLEASE PROVIDE THE SPECS. FOR THE EXHAUST FANS. |
| PLEASE SHOW ON PLAN THE EXHAUST DUCT AND TERMINATION |
| POINTS FOR THE BATH EXHAUSTS. |
| |
| 4) PLEASE SHOW AN EXHAUST FAN FOR THE MASTER BATHROOM, |
| SHOWER AREA. FBC M BATHROOM DEFINITION; FBC RES , FBC M |
| TABLE 403.3.1.1; FBC RES TABLE M1507.4 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |