Plan Review Notes
Plan Review Notes For Permit 20040979
Permit Number 20040979
Review Stop M
Sequence Number 1
Notes
Date Text
2020-06-16 13:24:411ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20040979
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SPECS SHEETS AND CALCULATIONS FOR
 HEATING AND COOLING EQUIPMENT SIZING FOR THIS ADDITION.
 FBC EC M403.7; FBC EC 101.5.1.1.2
  
 2) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE
 MECHANICAL SYSTEM FOR THIS ADDITION.
  
 3) PLEASE PROVIDE THE SPECS. FOR THE EXHAUST FANS.
 PLEASE SHOW ON PLAN THE EXHAUST DUCT AND TERMINATION
 POINTS FOR THE BATH EXHAUSTS.
  
 4) PLEASE SHOW AN EXHAUST FAN FOR THE MASTER BATHROOM,
 SHOWER AREA. FBC M BATHROOM DEFINITION; FBC RES , FBC M
 TABLE 403.3.1.1; FBC RES TABLE M1507.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  