2020-06-22 08:49:02PLAN REVIEW - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE NEW PANEL SCHEDULE. IDENTIFY NEW AND
 EXISTING CIRCUTS.
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 2. PROVIDE UPDATED LOAD CALCULATIONS.
 PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL LOADS
 FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS FOR
 THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2.
  
  
  
  