2020-04-30 08:31:58 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) INDICATE THE ATTACHMENT METHOD THAT WILL BE USED TO | | INSTALL THE ROOF TILE BY MARKING THE SPECIFIC | | ATTACHMENT METHOD AND ATTACHMENT RESISTANCE FROM THE | | ONES LISTED IN THE ROOF TILE PRODUCT APPROVAL. CITY | | AMENDMENTS FBC 107.1.2 | | | | 2) THE PRODUCT APPROVAL FOR THE BORAL TILESEAL DOES NOT | | SPECIFY A VALUE FOR IT'S DESIGN PRESSURE TO RESIST | | UPLIFT. IF THE ROOF TILE IS BEING INSTALLED WITH AN | | ADHESIVE YOU WILL HAVE TO SUBMIT A PRODUCT APPROVAL | | THAT LISTS A MAXIMUM DESIGN PRESSURE FOR THE TILE | | UNDERLAYMENT. FBC R905.1 |
|