2020-06-16 13:55:06 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN |
| KITCHEN, INCLUDING THE ISLAND, REQUIRE GFCI PROTECTION. |
| SOME AREAS REQUIRE AFCI AND GFCI PROTECTION. PROVIDE |
| CORRECTION. NEC 210.8, 210.12 |
| 2. PROVIDE LAYOUT OF EXISTING RECEPTACLE OUTLETS IN |
| KITCHEN TO CONFIRM CODE COMPLIANCE. WPB FBC 107.2.1 |
| 3. LOAD CALCULATION USES 240 VOLT FOR THE CALCULATION. |
| MOST BUIDLINGS OF THIS TYPE HAVE A 208 VOLT 3 PHASE |
| SYSTEM. PROVIDE CLARIFICATIOIN AND/OR CORRECTION FOR |
| LOAD CALCULATION AS NEEDED. NEC 110.4, 220.5 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| |