2020-06-16 13:55:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN, INCLUDING THE ISLAND, REQUIRE GFCI PROTECTION.
 SOME AREAS REQUIRE AFCI AND GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8, 210.12
 2. PROVIDE LAYOUT OF EXISTING RECEPTACLE OUTLETS IN
 KITCHEN TO CONFIRM CODE COMPLIANCE. WPB FBC 107.2.1
 3. LOAD CALCULATION USES 240 VOLT FOR THE CALCULATION.
 MOST BUIDLINGS OF THIS TYPE HAVE A 208 VOLT 3 PHASE
 SYSTEM. PROVIDE CLARIFICATIOIN AND/OR CORRECTION FOR
 LOAD CALCULATION AS NEEDED. NEC 110.4, 220.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  