2020-05-05 14:11:59 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20040884 |
| |
| CODES IN EFFECT: |
| |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE SUBMIT A MECHANICAL DRAWING SHOWING THE |
| REQUIRED HEATING OF THIS NEW SPACE. PLEASE SHOW HOW YOU |
| ARE GOING TO CONDITION THIS NEW BEDROOM. IF YOU ARE |
| GOING TO USE EXISTING MECHANICAL SYSTEM, PLEASE SHOW |
| THE EXISTING SYSTEM IS SIZED TO ACCOMMODATE THE |
| ADDITIONAL LOAD. PROVIDE ENERGY SUBMITTAL AND MANUAL J. |
| FBC FS 107.2, FBC EC 101.5.1.1.2 |
| |
| 2) THIS WILL REQUIRE A MECHANICAL SUB-PERMIT. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |