Plan Review Notes For Permit 20040884
Permit Number 20040884
Review Stop B
Sequence Number 1
Notes
Date Text
2020-05-22 11:06:00PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUATION
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS.
  
 BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE
 DETERMINED AT THIS TIME.
  
 1. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
 2. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 3. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
 4. FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
 PLEASE INCREASE THE VALUATION ACCORDINGLY.
  
 2. DESIGNER SHALL PROVIDE INSULATION VALUES FOR CEILING
 AND WALLS.
 PROVIDE AN ENERGY SUBMITTAL.
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 3. PROVIDE FRAMING DETAILS FOR EXTERIOR WALLS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. PROVIDE WINDOW SCHEDULE. INCLUDE ROUGH OPENINGS AND
 DESIGN PRESSURES.
 THESE MAY BE PLACED ON THE PLAN NEXT TO EACH OPENING.
 1709.5 EXTERIOR WINDOW AND DOOR ASSEMBLIES.
 THE DESIGN PRESSURE RATING OF EXTERIOR WINDOWS AND
 DOORS IN BUILDINGS SHALL BE DETERMINED IN ACCORDANCE
 WITH SECTION 1709.5.1 OR 1709.5.2. FOR THE PURPOSES OF
 THIS SECTION, THE REQUIRED DESIGN PRESSURE SHALL BE
 DETERMINED USING THE ALLOWABLE STRESS DESIGN LOAD
 COMBINATIONS OF SECTION 1605.3.
  
 5. PROVIDE PRODUCT APPROVALS FOR PROPOSED WINDOWS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW SUBMITTALS.
  
 6. IDENTIFY MEANS OF EGRESS FROM PROPOSED BEDROOM.
  
 R311.1MEANS OF EGRESS.
 DWELLINGS SHALL BE PROVIDED WITH A MEANS OF EGRESS IN
 ACCORDANCE WITH THIS SECTION. THE MEANS OF EGRESS SHALL
 PROVIDE A CONTINUOUS AND UNOBSTRUCTED PATH OF VERTICAL
 AND HORIZONTAL EGRESS TRAVEL FROM ALL PORTIONS OF THE
 DWELLING TO THE REQUIRED EGRESS DOOR WITHOUT REQUIRING
 TRAVEL THROUGH A GARAGE. THE REQUIRED EGRESS DOOR SHALL
 OPEN DIRECTLY INTO A PUBLIC WAY OR TO A YARD OR COURT
 THAT OPENS TO A PUBLIC WAY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  