2020-05-22 11:06:00 | PLAN REVIEW - BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. VALUATION |
| |
| CITY OF WPB CHPT. 1 ? VALUE |
| 109.3 BUILDING PERMIT VALUATIONS. |
| |
| BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE |
| DETERMINED AT THIS TIME. |
| |
| 1. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE |
| OF WORK. |
| 2. THE PERMIT VALUATION AND PERMIT FEE MUST BE |
| COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED |
| CONTRACTOR WOULD PROVIDE. |
| 3. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE |
| OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT |
| RENTAL TO VERIFY VALUE. |
| 4. FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| BUILDING OFFICIAL. |
| PLEASE INCREASE THE VALUATION ACCORDINGLY. |
| |
| 2. DESIGNER SHALL PROVIDE INSULATION VALUES FOR CEILING |
| AND WALLS. |
| PROVIDE AN ENERGY SUBMITTAL. |
| FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| |
| 3. PROVIDE FRAMING DETAILS FOR EXTERIOR WALLS. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. PROVIDE WINDOW SCHEDULE. INCLUDE ROUGH OPENINGS AND |
| DESIGN PRESSURES. |
| THESE MAY BE PLACED ON THE PLAN NEXT TO EACH OPENING. |
| 1709.5 EXTERIOR WINDOW AND DOOR ASSEMBLIES. |
| THE DESIGN PRESSURE RATING OF EXTERIOR WINDOWS AND |
| DOORS IN BUILDINGS SHALL BE DETERMINED IN ACCORDANCE |
| WITH SECTION 1709.5.1 OR 1709.5.2. FOR THE PURPOSES OF |
| THIS SECTION, THE REQUIRED DESIGN PRESSURE SHALL BE |
| DETERMINED USING THE ALLOWABLE STRESS DESIGN LOAD |
| COMBINATIONS OF SECTION 1605.3. |
| |
| 5. PROVIDE PRODUCT APPROVALS FOR PROPOSED WINDOWS. |
| FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| SPECIFICALLY, PROVIDE WINDOW SUBMITTALS. |
| |
| 6. IDENTIFY MEANS OF EGRESS FROM PROPOSED BEDROOM. |
| |
| R311.1MEANS OF EGRESS. |
| DWELLINGS SHALL BE PROVIDED WITH A MEANS OF EGRESS IN |
| ACCORDANCE WITH THIS SECTION. THE MEANS OF EGRESS SHALL |
| PROVIDE A CONTINUOUS AND UNOBSTRUCTED PATH OF VERTICAL |
| AND HORIZONTAL EGRESS TRAVEL FROM ALL PORTIONS OF THE |
| DWELLING TO THE REQUIRED EGRESS DOOR WITHOUT REQUIRING |
| TRAVEL THROUGH A GARAGE. THE REQUIRED EGRESS DOOR SHALL |
| OPEN DIRECTLY INTO A PUBLIC WAY OR TO A YARD OR COURT |
| THAT OPENS TO A PUBLIC WAY. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |