Plan Review Notes
Plan Review Notes For Permit 20040867
Permit Number 20040867
Review Stop P
Sequence Number 3
Notes
Date Text
2021-12-16 14:42:031ST REVIEW FBC-2020 PLUMBING
 PERMIT- 20040867
 12/16/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 WPB CROSS CONNECTION CONTROL MANUAL- WPB CCCM
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: 3RD REQUEST FOR CIVIL DRAWINGS AND
 BACKFLOW PREVENTER SPECIFICATIONS. COPIED BELOW ARE THE
 1ST AND 2ND PLUMBING REVIEW COMMENTS REQUESTING THE
 DRAWINGS AND BACKFLOW PREVENTER LOCATION AND SPECS. THE
 ENGINEER'S RESPONSE NARRATIVE INDICATE THE PDF'S WERE
 SUBMITTED HOWEVER IT APPEARS THEY WERE NOT UPLOADED FOR
 REVIEW. THE PLANS SETS SHALL INCLUDE WATER/SEWER AND
 DRAINAGE PLANS. WATER/SEWER SHALL SHOW LOCATIONS OF
 WATER MAIN, POINT OF WATER SERVICE CONNECTION, METER
 AND BACKFLOW LOCATION, SEWER LATERAL, SEWER/BUILDING
 DRAIN POINT OF CONNECTION. DRAINAGE PLANS SHALL SHOW
 STORM DRAIN LATERAL AND BUILDING STORM DRAIN POINTS OF
 CONNECTION, AND/OR LOCATIONS OF ROOF DRAINAGE AREAS,
 AND CATCH BASINS- SECS. 107.2.1, 110.9 WPB AND SEC.
 1101.2 FBC P.
  
 PREVIOUS PLUMBING COMMENTS:
 D. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, WPB CCCM
 AND FBC PL 608, PROVIDE SPECIFICATION, DETAIL AND
 LOCATION FOR THE WATER SERVICE BACKFLOW PREVENTER.
 RESPONSE: CIVIL DRAWINGS TO ADDRESS.
 NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE CIVIL
 DRAWINGS; PROVIDE SPECIFICATION, DETAIL AND LOCATION
 FOR THE WATER SERVICE BACKFLOW PREVENTER COMPLYING WITH
 WPB CCCM AND FBC PL 608.
 E. SECOND REQUEST; SEE PLAN SHEET P.1: PER WPB FBC
 107.2.1, PROVIDE CIVIL DRAWINGS NOTED AT SERVICE
 CONNECTIONS.
 PLEASE NOTE: A PLUMBING PERMIT WILL NOT BE ISSUED WITH
 OUT THE CIVIL DRAWINGS SHOWING THE REQUESTED
 INFORMATION FOR THE BACKFLOW PREVENTER. WPB FBC
 107.2.1.2.
  
 NEW COMMENT: A SEPARATE PERMIT IS REQUIRED FOR
 ISTALLATION OF THE POTABLE WATER SERVICE BACKFLOW
 PRVENTER.
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  