Plan Review Notes
Plan Review Notes For Permit 20040867
Permit Number 20040867
Review Stop B
Sequence Number 3
Notes
Date Text
2021-12-01 09:14:14WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040867
 ADD: 936 27TH ST.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] CONTACT: MATTHEW DONNELL
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. AUGUST 03RD/ 2020
 ACTION: DENIED
  
 1) COMPLIED. VALUATION.
  
 2) COMPLIED.
  
  
 3A-B) COMPLIED.
  
 3C)PROVISO/ NOTICE NO ACTION REQUIRED. THERE IS A
 DETAIL FOR THE DUMPSTER ENCLOSURE, PLEASE NOTE THE
 DUMPSTER ENCLOSURE TAKES A SEPARATE, REVIEW AND
 ASSOCIATED FEES.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE 105.1.
  
 3D) PROVISO/ NOTICE NO ACTION REQUIRED. JUST TO THE
 RIGHT OF THE FLOOR PLAN SHOWS A CONCRETE SLAB WITH (3)
 500 GALLON FUEL TANKS. FUEL TANKS ALSO TAKE SEPARATE
 PERMITS REVIEWS AND ASSOCIATED FEES. 2017 FLORIDA
 BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 105.1.
  
 3E) NOT APPLICABLE.
  
 4) SHEET 003 4.1 COMPLIED PRESSURES IN VASD. THANK YOU.
  
  
 5) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS, THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 6A) 2ND REQUEST. FOR METAL BUILDINGS THE WALL AND ROOF
 PRODUCT APPROVALS ARE REQUIRED BEFORE PERMIT ISSUANCE
 JUST AS THE BUILDING SHOP DRAWINGS ARE REQUIRED, TO
 VERIFY GIRT & PURLIN SPACING AND PRESSURES MATCH FOR
 THE WALL END ZONE 5 AND ROOF CORNER ZONE 3. MOST OF THE
 TIME THE GIRTS AND PURLINS NEED TO BE SPACED CLOSER
 TOGETHER FOR THE HIGHER PRESSURES IN THESE ZONES.
 COMPONENTS & CLADDING PLEASE SUPPLY THE PRODUCT
 APPROVAL FULL REPORTS. IF IN THE PRODUCT APPROVAL THERE
 ARE MULTIPLE SUB-SYSTEMS APPROVED IDENTIFY (CIRCLE)
 WHICH APPLICATION IS TO BE INSTALLED.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: METAL WALL PANELS, LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, METAL ROOF PANELS,
  
 6B) 3RD REQUEST. RESPONSE COMMENT INDICATES WALL AND
 ROOF PANEL PRODUCT APPROVALS ATTACHED. NO PRODUCT
 APPROVALS ARE ATTACHED.
 W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6C) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 7) THE SHEETS SUBMITTED BY MBMI 4/ 10 ROOF FRAMING
 PURLIN SPACING @ 3FEET 5 ? INCH SPACING & GIRTS AND
 SHEET 5/10 END WALL AND SIDE WALL FRAMING WITH VARIED
 SPACING, BUT IN THE END WALL ZONES SAME SPACING AS WALL
 ZONE 4. NEED PRODUCT APPROVALS TO VERIFY SPACING AND
 THE ASSOCIATED PRESSURES.
 THE MISSING INFORMATION IS THE PRODUCT APPROVAL FOR THE
 METAL EXTERIOR WALL SYSTEM AND METAL ROOF SYSTEM.
 WITHOUT THE PRODUCT APPROVALS BEING SUBMITTED,
 IDENTIFYING THE TYPE OF WALL AND ROOF PANELS BEING
 INSTALLED, WITH THEIR ALLOWABLE SPACING BETWEEN
 SUPPORTS AND ASSOCIATED PRESSURES NO REVIEW FOR THE
 STRUCTURAL PORTION OF THE BUILDING CAN BE COMPLETED.
  
 8) SEMI COMPLIED. IS THE ENGINEER FOR MBMI TAKING THE
 DOUBLE REDUCTION IN ROOF PANEL PRESSURES, IT IS NOT
 STATED, AND WITHOUT THE ROOFING PRODUCT APPROVAL
 VERIFICATION OF ROOF DESIGN PANEL AND TYPE OF PANEL
 LOCKING DEVICE CANNOT BE VERIFIED.
 THE OTHER UNKNOWN IS IF THE ENGINEER OF RECORD FOR MBMI
 HAS DESIGNED THE ROOF SYSTEM TO SECTION 2211.5 OF THE
 FBC-B AISI S210 OR AISI S 100? WITH A GREATER DEDUCTION
 IN PRESSURES THAN ALLOWED IN VASD?
  
 9) NEW COMMENT. MBMI SHEET 6 END WALL FRAMING LINE 3
 EC-2 SIDE SHOWS 6 GIRTS WHEREAS SIDE EC-5 ONLY SHOWS 5.
 END WALL FRAMING LEFT SIDE ON THE LEFT SIDE IT IS
 DIMENSIONED AS A GIRT BEING THERE BUT NOT SHOWN AGAIN
 THE RIGHT SIDE DOES NOT SHOW BUT 5 GIRTS. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 10) NEW COMMENT. SITE PLAN SP-1 CHANGE SHOWS THE
 PROPOSED BUILDING 5 FEET FROM THE PROPERTY LINE. WITH
 THE BUILDING TYPE BEING DECLARED TYPE IIB/ S1
 OCCUPANCY, AND 5 FEET FROM THE PROPERTY LINE THIS WALL
 WILL NEED TO BE 1 HOUR FIRE RATED PER TABLE 602 OF THE
 2020 FBC-BUILDING CODE.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN ( NO
 PRODUCT APPROVALS) SINCE THERE WAS A GREAT DEFICIENCY
 IN PLANS AND REQUIRED DOCUMENTATION. WITH THE NEXT PLAN
 REVIEW CYCLE THERE MAYBE ADDITIONAL REVIEW COMMENTS
 BECAUSE OF NEW PLANS AND INFORMATION LACKING UNDER THE
 PRIOR REVIEW.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  