2021-12-01 09:14:14 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20040867 |
| ADD: 936 27TH ST. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: ??? |
| E-MAIL: [email protected] CONTACT: MATTHEW DONNELL |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2ND REVIEW |
| DATE: TUES. AUGUST 03RD/ 2020 |
| ACTION: DENIED |
| |
| 1) COMPLIED. VALUATION. |
| |
| 2) COMPLIED. |
| |
| |
| 3A-B) COMPLIED. |
| |
| 3C)PROVISO/ NOTICE NO ACTION REQUIRED. THERE IS A |
| DETAIL FOR THE DUMPSTER ENCLOSURE, PLEASE NOTE THE |
| DUMPSTER ENCLOSURE TAKES A SEPARATE, REVIEW AND |
| ASSOCIATED FEES. |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATIVE CODE 105.1. |
| |
| 3D) PROVISO/ NOTICE NO ACTION REQUIRED. JUST TO THE |
| RIGHT OF THE FLOOR PLAN SHOWS A CONCRETE SLAB WITH (3) |
| 500 GALLON FUEL TANKS. FUEL TANKS ALSO TAKE SEPARATE |
| PERMITS REVIEWS AND ASSOCIATED FEES. 2017 FLORIDA |
| BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE |
| 105.1. |
| |
| 3E) NOT APPLICABLE. |
| |
| 4) SHEET 003 4.1 COMPLIED PRESSURES IN VASD. THANK YOU. |
| |
| |
| 5) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS, THE |
| CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| BE REQUIRED. |
| 2017 FBC-B 2204.1 WELDING |
| 1. WELD PROCEDURES SPECIFICATIONS |
| 2. QUALIFICATIONS OF WELDING PERSONAL |
| 2017 FBC-B 2204.2 BOLTING. |
| IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| AT |
| 561-805-6666. |
| |
| 6A) 2ND REQUEST. FOR METAL BUILDINGS THE WALL AND ROOF |
| PRODUCT APPROVALS ARE REQUIRED BEFORE PERMIT ISSUANCE |
| JUST AS THE BUILDING SHOP DRAWINGS ARE REQUIRED, TO |
| VERIFY GIRT & PURLIN SPACING AND PRESSURES MATCH FOR |
| THE WALL END ZONE 5 AND ROOF CORNER ZONE 3. MOST OF THE |
| TIME THE GIRTS AND PURLINS NEED TO BE SPACED CLOSER |
| TOGETHER FOR THE HIGHER PRESSURES IN THESE ZONES. |
| COMPONENTS & CLADDING PLEASE SUPPLY THE PRODUCT |
| APPROVAL FULL REPORTS. IF IN THE PRODUCT APPROVAL THERE |
| ARE MULTIPLE SUB-SYSTEMS APPROVED IDENTIFY (CIRCLE) |
| WHICH APPLICATION IS TO BE INSTALLED. |
| 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: METAL WALL PANELS, LOUVERS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, METAL ROOF PANELS, |
| |
| 6B) 3RD REQUEST. RESPONSE COMMENT INDICATES WALL AND |
| ROOF PANEL PRODUCT APPROVALS ATTACHED. NO PRODUCT |
| APPROVALS ARE ATTACHED. |
| W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 6C) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| REVIEW. |
| |
| 7) THE SHEETS SUBMITTED BY MBMI 4/ 10 ROOF FRAMING |
| PURLIN SPACING @ 3FEET 5 ? INCH SPACING & GIRTS AND |
| SHEET 5/10 END WALL AND SIDE WALL FRAMING WITH VARIED |
| SPACING, BUT IN THE END WALL ZONES SAME SPACING AS WALL |
| ZONE 4. NEED PRODUCT APPROVALS TO VERIFY SPACING AND |
| THE ASSOCIATED PRESSURES. |
| THE MISSING INFORMATION IS THE PRODUCT APPROVAL FOR THE |
| METAL EXTERIOR WALL SYSTEM AND METAL ROOF SYSTEM. |
| WITHOUT THE PRODUCT APPROVALS BEING SUBMITTED, |
| IDENTIFYING THE TYPE OF WALL AND ROOF PANELS BEING |
| INSTALLED, WITH THEIR ALLOWABLE SPACING BETWEEN |
| SUPPORTS AND ASSOCIATED PRESSURES NO REVIEW FOR THE |
| STRUCTURAL PORTION OF THE BUILDING CAN BE COMPLETED. |
| |
| 8) SEMI COMPLIED. IS THE ENGINEER FOR MBMI TAKING THE |
| DOUBLE REDUCTION IN ROOF PANEL PRESSURES, IT IS NOT |
| STATED, AND WITHOUT THE ROOFING PRODUCT APPROVAL |
| VERIFICATION OF ROOF DESIGN PANEL AND TYPE OF PANEL |
| LOCKING DEVICE CANNOT BE VERIFIED. |
| THE OTHER UNKNOWN IS IF THE ENGINEER OF RECORD FOR MBMI |
| HAS DESIGNED THE ROOF SYSTEM TO SECTION 2211.5 OF THE |
| FBC-B AISI S210 OR AISI S 100? WITH A GREATER DEDUCTION |
| IN PRESSURES THAN ALLOWED IN VASD? |
| |
| 9) NEW COMMENT. MBMI SHEET 6 END WALL FRAMING LINE 3 |
| EC-2 SIDE SHOWS 6 GIRTS WHEREAS SIDE EC-5 ONLY SHOWS 5. |
| END WALL FRAMING LEFT SIDE ON THE LEFT SIDE IT IS |
| DIMENSIONED AS A GIRT BEING THERE BUT NOT SHOWN AGAIN |
| THE RIGHT SIDE DOES NOT SHOW BUT 5 GIRTS. 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 10) NEW COMMENT. SITE PLAN SP-1 CHANGE SHOWS THE |
| PROPOSED BUILDING 5 FEET FROM THE PROPERTY LINE. WITH |
| THE BUILDING TYPE BEING DECLARED TYPE IIB/ S1 |
| OCCUPANCY, AND 5 FEET FROM THE PROPERTY LINE THIS WALL |
| WILL NEED TO BE 1 HOUR FIRE RATED PER TABLE 602 OF THE |
| 2020 FBC-BUILDING CODE. |
| |
| 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN ( NO |
| PRODUCT APPROVALS) SINCE THERE WAS A GREAT DEFICIENCY |
| IN PLANS AND REQUIRED DOCUMENTATION. WITH THE NEXT PLAN |
| REVIEW CYCLE THERE MAYBE ADDITIONAL REVIEW COMMENTS |
| BECAUSE OF NEW PLANS AND INFORMATION LACKING UNDER THE |
| PRIOR REVIEW. |
| |
| MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE |
| WORKING FROM CITY HALL. |
| MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |