Date |
Text |
2021-08-05 16:27:54 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20040867 936 27TH ST |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| A.NEW COMMENTS REGARDING ICE MACHINE IN SCOPE OF WORK: |
| 1.PER WPB FBC 107.2.1, SHOW COLD WATER ROUTING TO ICE |
| MACHINE ON FLOOR PLAN TO MATCH RISER DIAGRAM. |
| 2.PER FBC PL 606.2.2 AND 606.3, PROVIDE DEDICATED, |
| ACCESSIBLE SHUT OFF VALVE FOR HOSE BIB AT ICE MACHINE |
| VICINITY |
| 3.PER FBC PL 606.2.3 AND 606.3, PROVIDE DEDICATED, |
| ACCESSIBLE SHUT OFF VALVE FOR ICE MACHINE. |
| |
| |
| B.NEW COMMENT REGARDING RECIRCULATING PUMP PIPING |
| DETAIL: |
| PER FBC 107.2.1, |
| 1.SHOW COLD WATER TO WATER HEATER; SHOW SHUT OFF VALVE |
| AT UPSTREAM END, FOLLOWED BY CHECK VALVE, THEN |
| EXPANSION TANK THEN RETURN CONNECTION, THEN CONNECTION |
| TO WATER HEATER. |
| 2.SHOW RETURN WITH BALL VALVE AT UPSTREAM END, FOLLOWED |
| BY CHECK VALVE THEN THE PUMP AND CONNECTION TO COLD |
| WATER |
| |
| C. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, PROVIDE A |
| NOTE STATING ?ALL PIPING SHALL BE SUPPORTED IN |
| ACCORDANCE WITH 2017 FBC PLUMBING CODE SECTION 308?. |
| COMPLIED |
| NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE HANGER DETAIL |
| WITH HANGER TYPE, ROD AND ATTACHMENTS TO STRUCTURE. |
| |
| D. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, WPB CCCM |
| AND FBC PL 608, PROVIDE SPECIFICATION, DETAIL AND |
| LOCATION FOR THE WATER SERVICE BACKFLOW PREVENTER. |
| RESPONSE: CIVIL DRAWINGS TO ADDRESS. |
| NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE CIVIL |
| DRAWINGS; PROVIDE SPECIFICATION, DETAIL AND LOCATION |
| FOR THE WATER SERVICE BACKFLOW PREVENTER COMPLYING WITH |
| WPB CCCM AND FBC PL 608. |
| |
| E. SECOND REQUEST; SEE PLAN SHEET P.1: PER WPB FBC |
| 107.2.1, PROVIDE CIVIL DRAWINGS NOTED AT SERVICE |
| CONNECTIONS. |
| PLEASE NOTE: A PLUMBING PERMIT WILL NOT BE ISSUED WITH |
| OUT THE CIVIL DRAWINGS SHOWING THE REQUESTED |
| INFORMATION FOR THE BACKFLOW PREVENTER. WPB FBC |
| 107.2.1.2. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |
| 20040867 936 27TH ST |