Date |
Text |
2020-06-29 14:28:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET 3.1 - THEE IS AN INDICATION OF A FIRE |
| SPRINKLER SYSTEM; HOWEVER, THERE ARE NO REQUIRED F.A.C. |
| 61G DOCUMENTS. |
| |
| AN ENGINEER OF RECORD IS REQUIRED TO SUBMITT F.A.C. 61G |
| DOCUMENTS FOR WATER BASED FIRE PROTECTION |
| |
| PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| PRE-ENGINEERED SYSTEMS. |
| |
| 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING |
| DOCUMENTS. |
| (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF |
| PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR |
| INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING |
| PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER?S |
| RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31, |
| 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING |
| CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE AHJ. THE DOCUMENTS SHALL INCLUDE: |
| (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS |
| REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A |
| RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND |
| EXPERIENCE. |
| (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY |
| STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH |
| THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS |
| ARE INTENDED TO CONFORM TO. |
| (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF |
| RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF |
| THE SYSTEM. |
| (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT |
| SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING |
| DOCUMENTS. |
| (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY |
| FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE |
| ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE |
| STATED PURPOSE OF THESE RESPONSIBILITY RULES. |
| (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND |
| BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING |
| DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR |
| CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE |
| OF SUCH DOCUMENTS. |
| (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN |
| ENGINEERING DOCUMENT ONLY FOR INFORMATION OR |
| CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO |
| ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER |
| SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS |
| RESPONSIBILITY. |
| (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY |
| DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST |
| ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS. |
| (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY |
| ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN |
| FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC |
| AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND |
| INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE |
| REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES |
| WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE |
| AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A |
| PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR |
| AGENCY APPROVAL ACTION ON THE SAME PROJECT. |
| |
| SEPARATE SHOP DRAWINGS SHALL THEN BE SUBMITTED UNDER A |
| SEPARATE PERMIT FOR INSTALLATION PURPOSES. |
| |
| PLEASE REVIEW AND PROVIDE |
| |
| |
| |
| |
| 2) SHEET E 1 & E 2 - THE FIRE SPRINKLER SYSTEM IS |
| REQUIRED TO BE MONITORED. |
| |
| PER NFPA 101 CH 9 |
| |
| 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| 9.6.1* GENERAL. |
| 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY |
| WHERE |
| SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS CODE |
| OR WHERE |
| SUPERVISION OF A NEW FIRE SPRINKLER SYSTEM OR NEW FIRE |
| ALARM |
| SYSTEM IS REQUIRED BY THE FLORIDA BUILDING CODE. |
| |
| ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT |
| AND SHOP DRAWINGS. |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| ACKNOWLEDGEMENT |
| |
| |
| |
| |
| 3) SHEET 3.1 - THERE IS AN INDICATION OF 3 FUEL TANKS |
| BU OTHERS. |
| |
| THE INSTALLATION OF THESE TANKS IS NOT APPROVIDE UNDER |
| THIS PERMIT AND ANY WORK INVLOVING THESE TANKS SHALL BE |
| DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| ACKNOWLEDGEMENT |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |