Plan Review Notes For Permit 20040867 |
Permit Number |
20040867 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-31 16:16:54 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PAGE E-2 | | | | 1) AIC RATING OF SERVICE AND PANEL PER 110.9, 110,10 | | | | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10 | | | | PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED | | WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT | | AVAILABLE PER NEC 110.24. | | | | PAGE E-1 | | | | 1) LIGHTING CONTROL PER FBC EEC REQUIRED | | |
|