Plan Review Notes
Plan Review Notes For Permit 20040867
Permit Number 20040867
Review Stop B
Sequence Number 1
Notes
Date Text
2020-07-12 13:33:08WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040867
 ADD: 936 27TH ST.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] CONTACT: MATTHEW DONNELL
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: SUN. JULY 12TH/ 2020
 ACTION: DENIED
  
 1) THE BUILDING VALUE IS LOW, LESS THAN ? OF THE VALUE
 FOR THE SQUARE FOOTAGE OF THE PROPOSED BUILDING. THE
 SUBMITTED VALUE OF THE PROPOSED BUILDING A (S1
 OCCUPANCY STORAGE OR MOTOR VEHICLE REPAIR GARAGE) PER
 SQ. FT. IS $28.57 DOLLARS / SQ. FT. $50.000.00/1750=
 $28.57. THE CALCULATED VALUE OF THE STRUCTURE WITHOUT
 FIRE SPRINKLERS IS $62.56 A SQ. FT. OR A PROPOSED
 CALCULATED VALUE OF $109,605.00 DOLLARS IN VALUE.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 2A) PLEASE PROVIDE EITHER A SITE PLAN AND OR SURVEY
 SHOWING THE LOCATION OF THE PROPOSED BUILDING AND ALL
 OTHER BUILDINGS AND OR STRUCTURES. 2017 FBC-B 503.1.2.
 & TABLE 602. SHOW DISTANCES FROM PROPERTY LINES AND
 OTHER STRUCTURES AND OR PROPOSED STRUCTURES.
  
 2B) THE PLANS PRODUCED BY GCP ARCHITECTURE LLC ARE NOT
 SIGNED NOR SEALED. NO SIGNATURE NOR SEAL. ARCHITECTS:
 FLORIDA ADMINISTRATIVE CODE 61G1-16.005. PROCEDURES FOR
 DIGITALLY SIGNING AND SEALING AND FOR ELECTRONICALLY
 TRANSMITTING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC...
  
 2C) THE SUBMITTED PLANS BY MBMI METAL BUILDINGS DOES
 NOT HAVE THE ENGINEERS SEAL WHO PREPARED THESE
 DRAWINGS. 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED
 & SEALED BY A PROFESSIONAL ENGINEER SHALL INCLUDE
 EITHER THE: NAME, ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS
 THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S.
 AND 471.023 F.S.).
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2D) THE ARCHITECT OF RECORD HAS NOT PUT THEIR SHOP
 DRAWING OF APPROVAL ON THE SUBMITTED DRAWING BY MBMI
 METAL BUILDINGS.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 3A) THERE IS NO LIFE SAFETY SHEET IN THIS SET OF PLANS.
 SHEET 002 3.1 IS A FLOOR PLAN WITH SOME REQUIREMENTS
 FROM THE NFPA BUT NONE OF THE REQUIREMENTS FOUND FOR
 THE 2017 FBC-B. FOR THIS REVIEW THE OCCUPANCY TYPE IS
 GOING TO BE CONSIDERED S1 A MOTOR VEHICLE REPAIR GARAGE
 COMPLYING WITH THE MAXIMUM QUANTITIES OF HAZARDOUS
 MATERIALS LISTED IN TABLE 307.1(1) SEE SECTION 406.8
  
 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
  
 MISSING CODE DATA:
 SET BACK / SEPARATION (ASSUMED PROPERTY LINES)
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
 IF IN A FLOOD ZONE. PROPOSED FLOOD ELEVATION
 CERTIFICATE FOR STRUCTURES IN A SPECIFIC FLOOD HAZARD
 AREAS
 OCCUPANCY GROUP
 MINIMUM TYPE OF CONSTRUCTION
 FIRE RESISTANCE SEPARATION
  
 LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE
 FOLLOWING:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 GROSS OR NET
 MEANS OF EGRESS EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 QUANTITIES OF HAZARDOUS MATERIALS TABLE 307.1(1).
 PROVIDE QUANTITIES AND STORAGE TYPE + MSDS SHEETS.
  
 3B) ACCESSIBILITY CODE DETAILS:
  
 3B)(1) IN THE FLOOR PLAN DETAIL THE DOOR SWINGS INTO
 THE CLEAR FLOOR SPACE OF THE LAV AND WATER CLOSET
 PLEASE SHOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY
 603.2.3 AND OR EXCEPTIONS ON THE DETAIL FLOOR PLAN.
  
 3B)(2) IN BOTH ELEVATION VIEWS 2 & 3 THE GRAB BARS FOR
 THE WATER CLOSET BOTH SHOW THE GRAB BARS BEING MEASURED
 FROM THE FINISH FLOOR TO THE CENTER LINE OF THE GRAB
 BAR. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION
 OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
  
 3C) THERE IS A DETAIL FOR THE DUMPSTER ENCLOSURE,
 PLEASE NOTE THE DUMPSTER ENCLOSURE TAKES A SEPARATE,
 REVIEW AND ASSOCIATED FEES.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE 105.1.
  
 3D) JUST TO THE RIGHT OF THE FLOOR PLAN SHOWS A
 CONCRETE SLAB WITH A ICE MACHINE AND (3) 500 GALLON
 FUEL TANKS. FUEL TANKS ALSO TAKE SEPARATE PERMITS
 REVIEWS AND ASSOCIATED FEES. 2017 FLORIDA BUILDING CODE
 W 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE 105.1.
  
 3E) THERE IS A NOTE ON THE PLANS THAT THE FIRE
 SPRINKLER SYSTEM IS TO MEET THE CODE REQUIREMENTS AND
 FIRE MARSHAL REQUIREMENTS.
 IN THE 2017 FBC-B THE REQUIREMENTS FOR FIRE SPRINKLERS
 FOR REPAIR GARAGES IS FOUND UNDER 903.2.9.1 FOR REPAIR
 GARAGES & 903.2.10.1 FOR COMMERCIAL PARKING GARAGES, IN
 BOTH CASES THE REQUIREMENT FOR FIRE SPRINKLERS WOULD BE
 IF THE FIRE AREA EXCEEDED 5,000 FEET. NOTE THE NFPA
 REQUIREMENTS MAYBE MORE RESTRICTIVE, IF SO WE ALWAYS
 USE THE MORE RESTRICTIVE CODE REQUIREMENT.
  
 4) SHEET 003 4.1 DOES SHOW A COMPONENTS AND CLADDING
 CHART FOR WALL ZONES 4 & 5 BUT THERE IS NO WIND DESIGN
 CRITERIA GIVEN.
 WITHIN THE PLANS DRAWN BY GCP ARCHITECTURAL GROUP THERE
 IS NO ROOF PLAN WITH THE ASSOCIATED COMPONENTS AND
 CLADDING FOR ROOF ZONES 1, 2, OR 3.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 4.2. RISK CATEGORY.
  
 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 4.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5) WELDED OR BOLTED CONNECTIONS, THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 6A) COMPONENTS & CLADDING PLEASE SUPPLY THE PRODUCT
 APPROVAL FULL REPORTS. IF IN THE PRODUCT APPROVAL THERE
 ARE MULTIPLE SUB-SYSTEMS APPROVED IDENTIFY (CIRCLE)
 WHICH APPLICATION IS TO BE INSTALLED.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: METAL WALL PANELS, STOREFRONTS,
 CURTAIN WALLS, WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, METAL ROOF PANELS,
 LIGHTWEIGHT CONCRETE INSULATION, ROOF TOP VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 6B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6C) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 7) THE SHEETS SUBMITTED BY MBMI 4/ 10 WALL FRAMING &
 GIRTS AND SHEET 5/10 END WALL AND ROOF FRAMING WITH
 PURLINS ARE SHOWN.
 THE MISSING INFORMATION IS THE PRODUCT APPROVAL FOR THE
 METAL EXTERIOR WALL SYSTEM AND METAL ROOF SYSTEM.
 WITHOUT THE PRODUCT APPROVALS BEING SUBMITTED,
 IDENTIFYING THE TYPE OF WALL AND ROOF PANELS BEING
 INSTALLED, WITH THEIR ALLOWABLE SPACING BETWEEN
 SUPPORTS AND ASSOCIATED PRESSURES NO REVIEW FOR THE
 STRUCTURAL PORTION OF THE BUILDING CAN BE COMPLETED.
  
 8) THE OTHER UNKNOWN IS IF THE ENGINEER OF RECORD FOR
 MBMI HAS DESIGNED THE ROOF SYSTEM TO SECTION 2211.5 OF
 THE FBC-B AISI S210 OR AISI S 100? WITH A GREATER
 DEDUCTION IN PRESSURES THAN ALLOWED IN VASD?
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  