2020-07-12 13:33:08 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20040867 |
| ADD: 936 27TH ST. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: ??? |
| E-MAIL: [email protected] CONTACT: MATTHEW DONNELL |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: SUN. JULY 12TH/ 2020 |
| ACTION: DENIED |
| |
| 1) THE BUILDING VALUE IS LOW, LESS THAN ? OF THE VALUE |
| FOR THE SQUARE FOOTAGE OF THE PROPOSED BUILDING. THE |
| SUBMITTED VALUE OF THE PROPOSED BUILDING A (S1 |
| OCCUPANCY STORAGE OR MOTOR VEHICLE REPAIR GARAGE) PER |
| SQ. FT. IS $28.57 DOLLARS / SQ. FT. $50.000.00/1750= |
| $28.57. THE CALCULATED VALUE OF THE STRUCTURE WITHOUT |
| FIRE SPRINKLERS IS $62.56 A SQ. FT. OR A PROPOSED |
| CALCULATED VALUE OF $109,605.00 DOLLARS IN VALUE. |
| 109.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| EACH PERMIT. |
| ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| PRIME OR MASTER PERMIT. |
| |
| 2A) PLEASE PROVIDE EITHER A SITE PLAN AND OR SURVEY |
| SHOWING THE LOCATION OF THE PROPOSED BUILDING AND ALL |
| OTHER BUILDINGS AND OR STRUCTURES. 2017 FBC-B 503.1.2. |
| & TABLE 602. SHOW DISTANCES FROM PROPERTY LINES AND |
| OTHER STRUCTURES AND OR PROPOSED STRUCTURES. |
| |
| 2B) THE PLANS PRODUCED BY GCP ARCHITECTURE LLC ARE NOT |
| SIGNED NOR SEALED. NO SIGNATURE NOR SEAL. ARCHITECTS: |
| FLORIDA ADMINISTRATIVE CODE 61G1-16.005. PROCEDURES FOR |
| DIGITALLY SIGNING AND SEALING AND FOR ELECTRONICALLY |
| TRANSMITTING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| DOCUMENTS. FL 61G1-23.015 (2) THE ARCHITECT IS |
| RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT |
| DATA, REPORTS, SHOP DRAWINGS ETC... |
| |
| 2C) THE SUBMITTED PLANS BY MBMI METAL BUILDINGS DOES |
| NOT HAVE THE ENGINEERS SEAL WHO PREPARED THESE |
| DRAWINGS. 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED |
| & SEALED BY A PROFESSIONAL ENGINEER SHALL INCLUDE |
| EITHER THE: NAME, ADDRESS AND LICENSE NUMBER OF THE |
| ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE |
| ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF |
| AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS |
| THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S. |
| AND 471.023 F.S.). |
| 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES), |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| DIGITALLY SIGNED AND SEALED ENGINEERING PLANS, |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| |
| 2D) THE ARCHITECT OF RECORD HAS NOT PUT THEIR SHOP |
| DRAWING OF APPROVAL ON THE SUBMITTED DRAWING BY MBMI |
| METAL BUILDINGS. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC... |
| |
| 3A) THERE IS NO LIFE SAFETY SHEET IN THIS SET OF PLANS. |
| SHEET 002 3.1 IS A FLOOR PLAN WITH SOME REQUIREMENTS |
| FROM THE NFPA BUT NONE OF THE REQUIREMENTS FOUND FOR |
| THE 2017 FBC-B. FOR THIS REVIEW THE OCCUPANCY TYPE IS |
| GOING TO BE CONSIDERED S1 A MOTOR VEHICLE REPAIR GARAGE |
| COMPLYING WITH THE MAXIMUM QUANTITIES OF HAZARDOUS |
| MATERIALS LISTED IN TABLE 307.1(1) SEE SECTION 406.8 |
| |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATIVE CODE SECTION: |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| OR STRUCTURES. |
| 107.3.5.1 COMMERCIAL BUILDINGS |
| 107.3.5.1.1. BUILDING |
| |
| MISSING CODE DATA: |
| SET BACK / SEPARATION (ASSUMED PROPERTY LINES) |
| FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD |
| ELEVATIONS |
| IF IN A FLOOD ZONE. PROPOSED FLOOD ELEVATION |
| CERTIFICATE FOR STRUCTURES IN A SPECIFIC FLOOD HAZARD |
| AREAS |
| OCCUPANCY GROUP |
| MINIMUM TYPE OF CONSTRUCTION |
| FIRE RESISTANCE SEPARATION |
| |
| LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE |
| FOLLOWING: |
| OCCUPANT LOAD AND EGRESS CAPACITIES |
| GROSS OR NET |
| MEANS OF EGRESS EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| QUANTITIES OF HAZARDOUS MATERIALS TABLE 307.1(1). |
| PROVIDE QUANTITIES AND STORAGE TYPE + MSDS SHEETS. |
| |
| 3B) ACCESSIBILITY CODE DETAILS: |
| |
| 3B)(1) IN THE FLOOR PLAN DETAIL THE DOOR SWINGS INTO |
| THE CLEAR FLOOR SPACE OF THE LAV AND WATER CLOSET |
| PLEASE SHOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY |
| 603.2.3 AND OR EXCEPTIONS ON THE DETAIL FLOOR PLAN. |
| |
| 3B)(2) IN BOTH ELEVATION VIEWS 2 & 3 THE GRAB BARS FOR |
| THE WATER CLOSET BOTH SHOW THE GRAB BARS BEING MEASURED |
| FROM THE FINISH FLOOR TO THE CENTER LINE OF THE GRAB |
| BAR. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION |
| OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A |
| HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| THE GRIPPING SURFACE, NOT CENTERLINE. |
| |
| 3C) THERE IS A DETAIL FOR THE DUMPSTER ENCLOSURE, |
| PLEASE NOTE THE DUMPSTER ENCLOSURE TAKES A SEPARATE, |
| REVIEW AND ASSOCIATED FEES. |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATIVE CODE 105.1. |
| |
| 3D) JUST TO THE RIGHT OF THE FLOOR PLAN SHOWS A |
| CONCRETE SLAB WITH A ICE MACHINE AND (3) 500 GALLON |
| FUEL TANKS. FUEL TANKS ALSO TAKE SEPARATE PERMITS |
| REVIEWS AND ASSOCIATED FEES. 2017 FLORIDA BUILDING CODE |
| W 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE 105.1. |
| |
| 3E) THERE IS A NOTE ON THE PLANS THAT THE FIRE |
| SPRINKLER SYSTEM IS TO MEET THE CODE REQUIREMENTS AND |
| FIRE MARSHAL REQUIREMENTS. |
| IN THE 2017 FBC-B THE REQUIREMENTS FOR FIRE SPRINKLERS |
| FOR REPAIR GARAGES IS FOUND UNDER 903.2.9.1 FOR REPAIR |
| GARAGES & 903.2.10.1 FOR COMMERCIAL PARKING GARAGES, IN |
| BOTH CASES THE REQUIREMENT FOR FIRE SPRINKLERS WOULD BE |
| IF THE FIRE AREA EXCEEDED 5,000 FEET. NOTE THE NFPA |
| REQUIREMENTS MAYBE MORE RESTRICTIVE, IF SO WE ALWAYS |
| USE THE MORE RESTRICTIVE CODE REQUIREMENT. |
| |
| 4) SHEET 003 4.1 DOES SHOW A COMPONENTS AND CLADDING |
| CHART FOR WALL ZONES 4 & 5 BUT THERE IS NO WIND DESIGN |
| CRITERIA GIVEN. |
| WITHIN THE PLANS DRAWN BY GCP ARCHITECTURAL GROUP THERE |
| IS NO ROOF PLAN WITH THE ASSOCIATED COMPONENTS AND |
| CLADDING FOR ROOF ZONES 1, 2, OR 3. |
| 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| |
| 4.2. RISK CATEGORY. |
| |
| 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| |
| 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| THE DESIGN OF THE STRUCTURE, PSF. |
| |
| 4.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 5) WELDED OR BOLTED CONNECTIONS, THE CONTRACTOR IS |
| REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE |
| WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. |
| 2017 FBC-B 2204.1 WELDING |
| 1. WELD PROCEDURES SPECIFICATIONS |
| 2. QUALIFICATIONS OF WELDING PERSONAL |
| 2017 FBC-B 2204.2 BOLTING. |
| IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED |
| PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| AT |
| 561-805-6666. |
| |
| 6A) COMPONENTS & CLADDING PLEASE SUPPLY THE PRODUCT |
| APPROVAL FULL REPORTS. IF IN THE PRODUCT APPROVAL THERE |
| ARE MULTIPLE SUB-SYSTEMS APPROVED IDENTIFY (CIRCLE) |
| WHICH APPLICATION IS TO BE INSTALLED. |
| 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: METAL WALL PANELS, STOREFRONTS, |
| CURTAIN WALLS, WALL LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, METAL ROOF PANELS, |
| LIGHTWEIGHT CONCRETE INSULATION, ROOF TOP VENTILATORS |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 6B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 6C) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| REVIEW. |
| |
| 7) THE SHEETS SUBMITTED BY MBMI 4/ 10 WALL FRAMING & |
| GIRTS AND SHEET 5/10 END WALL AND ROOF FRAMING WITH |
| PURLINS ARE SHOWN. |
| THE MISSING INFORMATION IS THE PRODUCT APPROVAL FOR THE |
| METAL EXTERIOR WALL SYSTEM AND METAL ROOF SYSTEM. |
| WITHOUT THE PRODUCT APPROVALS BEING SUBMITTED, |
| IDENTIFYING THE TYPE OF WALL AND ROOF PANELS BEING |
| INSTALLED, WITH THEIR ALLOWABLE SPACING BETWEEN |
| SUPPORTS AND ASSOCIATED PRESSURES NO REVIEW FOR THE |
| STRUCTURAL PORTION OF THE BUILDING CAN BE COMPLETED. |
| |
| 8) THE OTHER UNKNOWN IS IF THE ENGINEER OF RECORD FOR |
| MBMI HAS DESIGNED THE ROOF SYSTEM TO SECTION 2211.5 OF |
| THE FBC-B AISI S210 OR AISI S 100? WITH A GREATER |
| DEDUCTION IN PRESSURES THAN ALLOWED IN VASD? |
| |
| 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |