Plan Review Notes
Plan Review Notes For Permit 20040827
Permit Number 20040827
Review Stop P
Sequence Number 1
Notes
Date Text
2020-06-01 08:38:441ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20040827
 5/29/20
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A0.01: THE SCOPE OF WORK FOR THE PROJECT IS
 INDICATED AS A NEW INTERIOR BUILD-OUT HOWEVER THE PLANS
 ARE INDICATING RENOVATION WORK IN THE CORE AREA ONLY.
 CONCERNING THE PLUMBING PLEASE PROVIDE A CLEAR SCOPE OF
 WORK OUTLINE FOR THE RENOVATION- SECTION 107.2.1 AND
 ADDRESS THE LIST OF COMMENTS BELOW. A THOROUGH REVIEW
 OF THE PLUMBING PLANS CANNOT BE COMPLETED AT THIS TIME.
  
 2) PROVIDE PLUMBING FIXTURE CALCULATIONS BASED ON TABLE
 403.3 FBC P. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED NUMBER OF FIXTURES.
  
 3) PROVIDE DEMOLITION AND PROPOSED PLANS FOR THE
 EXISTING TOILET ROOMS INDICATING WHAT ELEMENTS OF
 CONSTRUCTION-WALLS, FLOORS, PLUMBING FIXTURES, STALLS,
 ACCESSORIES ETC. ARE BEING REMOVED, REPLACED OR NEWLY
 INSTALLED- SECTION 107.2.1 WPB.
  
 4) PROVIDE ENLARGED DIMENSIONED TOILET ROOM FLOOR PLANS
 AND DETAILS SHOWING COMPLIANCE WITH THE FBC-17
 ACCESSIBILITY. THE ENLARGED DRAWINGS SHALL SHOW:
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SECTION 604.3 FBC ACC.
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SECTION 606.2.
 C) TOILET COMPARTMENT WIDTH AND LENGTH MEASUREMENTS-
 SECTIONS 604.2-604.8. FBC ACC, AND SECTION 405.3.1 FBC
 P.
 D) TOILET COMPARTMENT DOOR WIDTHS, DOOR SWINGS, AND
 WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3
 FBC ACC.
 E) TURNING SPACE DIAMETERS- SECTION 304.3.
 F) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 OR PARTITIONS- SECTION 604.2.
  
 5) PROVIDE TOILET ROOM ELEVATION DRAWINGS INDICATING:
 A) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 B) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3.
 C) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 306.
 D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5.
 E) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS-
 SECTION 604.6.
 F) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR
 PAPER DISPENSERS- SECTION 604.7,
 G) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACES- SECTION 603.3.
  
 6) A1.11, P6.1, P6.2: TOILET ROOM 612 APPEARS TO BE
 DESIGNED AS AN ACCESSIBLE UNISEX TOILET ROOM, HOWEVER
 SEPARATE FACILITIES FOR MALE AND FEMALE USE ARE
 REQUIRED- SECTION 403.2 FBC P AND SECTION 213.2 FBC
 ACC.
  
 7) A1.11, P6.1, P6.2: REFER TO SECTION 211.1.2 FBC ACC,
 AND TABLE 404.3 FBC P. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH SECTIONS 602.1 ? 602.6, AND ONE SHALL
 COMPLY WITH 602.7. SECTION 602.7 REQUIRES THAT SPOUT
 OUTLETS FOR STANDING PERSONS SHALL BE 38 INCHES MINIMUM
 AND 43 INCHES MAXIMUM FROM THE FINISHED FLOOR. SHOW THE
 LOCATIONS OF THE FOUNTAIN AND SHOW:
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND
 602.5.
  
 8) SHOW THE LOCATION OF THE REQUIRED SERVICE SINK-
 TABLE 403.3. FBC P.
  
 9) P6.1 & P6.2: REVISE THE PLUMBING PLANS TO SHOW THE
 WATER SUPPLY LINES AND DWV PIPING FOR THE DRINKING
 FOUNTAIN AND SERVICE SINK- SECTION 107.2.1 WPB.
  
 10) P6.1: PROVIDE TRAP SEAL PRIMERS FOR THE FLOOR
 DRAINS- SECTION 1002.4.1.1.
  
 11) P6.1: THE 2" VENT FOR THE WATER CLOSETS SHALL
 CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE TWO
 MOST UPSTREAM WOMEN'S WATER CLOSETS- SECTION 914.2 FBC
 P.
  
 12) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE WATER HEATER- SECTION
 502.1 FBC P, AND PROVIDE THE UNIT'S EFFICIENCY RATING
 IN THE SCHEDULE- SECTION C404.2 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  