Plan Review Notes For Permit 20040821 |
Permit Number |
20040821 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-04-24 12:41:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP | | PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM | | OVER. | | | | THERE IS NO HYDRAULIC CALCULATION SUBMITTED THAT SHOWS | | THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE | | EXISTING SYSTEM DESIGN OR A DESIGN PROFESSIONAL | | STATEMENT THAT INDCATES THE HYDRALIC CALCULATIONS SHALL | | NOT BE AFFECTED BY THE INSTALLATION OF THE FLEX DROP. | | AND THAT THE SYTEM/SPRINKLER HEAD SHALL FUNCTION AS | | DESIGNED. | | | | PLEASE PROVIDE CALCULATIONS OR DESIGN PROFESSIONAL | | STATEMENT. | | | | | | | | 2) THERE ARE NO SPEC SHEETS FOR THE TYPE AND/OR SIZE OF | | THE FLEX DROP. | | | | PLEASE PROVIDE SHEETS THAT MATCH THE NEW FLEX DROP. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] |
|