Plan Review Notes
Plan Review Notes For Permit 20040821
Permit Number 20040821
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-04-24 12:41:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP
 PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM
 OVER.
  
 THERE IS NO HYDRAULIC CALCULATION SUBMITTED THAT SHOWS
 THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE
 EXISTING SYSTEM DESIGN OR A DESIGN PROFESSIONAL
 STATEMENT THAT INDCATES THE HYDRALIC CALCULATIONS SHALL
 NOT BE AFFECTED BY THE INSTALLATION OF THE FLEX DROP.
 AND THAT THE SYTEM/SPRINKLER HEAD SHALL FUNCTION AS
 DESIGNED.
  
 PLEASE PROVIDE CALCULATIONS OR DESIGN PROFESSIONAL
 STATEMENT.
  
  
  
 2) THERE ARE NO SPEC SHEETS FOR THE TYPE AND/OR SIZE OF
 THE FLEX DROP.
  
 PLEASE PROVIDE SHEETS THAT MATCH THE NEW FLEX DROP.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL