Plan Review Notes
Plan Review Notes For Permit 20040798
Permit Number 20040798
Review Stop P
Sequence Number 2
Notes
Date Text
2020-06-25 10:43:41 
 1) COMMUNITY POOLS THAT ARE ASSOCIATED WITH A PRIVATE
 RESIDENTIAL COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL
 FINANCIAL ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO
 THE EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT
 COVERED BY THE ADA ACCESSIBILITY REQUIREMENTS,
 INCLUDING PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES.
 IF A SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY
 IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS
 REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON
 THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER
 STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013-011. 2ND
 REQUEST.
 2) A HOSE BIBB IS REQUIRED WITHIN 25 FEET OF EACH
 RESTROOM PER FBC-BUILDING SEC. 454.1.6.1.4. SHOW THE
 LOCATION OF THE HOSE BIBBS ON THE PLAN.2ND REQUEST
 3) SHTS. OD100 & OD 105 - CLARIFY THE TERMINATION POINT
 OF THE OVERFLOW/WASTE DISCHARGE LINE. PER CITY
 ORDINANCE ARTICLE III, SEC. 90-126 (B)(5), SWIMMING
 POOL WATER MAY NOT DISCHARGE TO THE SANITARY SYSTEM
 WITHOUT PERMISSION FROM THE CITY. IN ADDITION, SWIMMING
 POOL WATER MAY NOT DISCHARGE TO THE CITY'S STORMWATER
 COLLECTION SYSTEM PER CITY ORDINANCE ARTICLE V, SEC.
 90-203 (A) WITHOUT PERMISSION FROM THE CITY. PLEASE
 CONTACT MANNY GONZALEZ IN THE CITY OF WEST PALM BEACH
 ENGINEERING DEPARTMENT AT 561- 494-1040 FOR FURTHER
 DIRECTION ON THIS ISSUE. 2ND REQUEST.
 6) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW
 PREVENTER.
 7) THE PLANS SHALL BE DIGITALLY SIGNED AND SEALED AS
 REQD. PER FL. ADMIN. CODE RULE 61G15-23.004,
 61G15-23.005. 2ND REQUEST.
  