2020-06-25 10:43:41 | |
| 1) COMMUNITY POOLS THAT ARE ASSOCIATED WITH A PRIVATE |
| RESIDENTIAL COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL |
| FINANCIAL ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO |
| THE EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT |
| COVERED BY THE ADA ACCESSIBILITY REQUIREMENTS, |
| INCLUDING PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES. |
| IF A SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY |
| IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS |
| REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON |
| THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER |
| STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013-011. 2ND |
| REQUEST. |
| 2) A HOSE BIBB IS REQUIRED WITHIN 25 FEET OF EACH |
| RESTROOM PER FBC-BUILDING SEC. 454.1.6.1.4. SHOW THE |
| LOCATION OF THE HOSE BIBBS ON THE PLAN.2ND REQUEST |
| 3) SHTS. OD100 & OD 105 - CLARIFY THE TERMINATION POINT |
| OF THE OVERFLOW/WASTE DISCHARGE LINE. PER CITY |
| ORDINANCE ARTICLE III, SEC. 90-126 (B)(5), SWIMMING |
| POOL WATER MAY NOT DISCHARGE TO THE SANITARY SYSTEM |
| WITHOUT PERMISSION FROM THE CITY. IN ADDITION, SWIMMING |
| POOL WATER MAY NOT DISCHARGE TO THE CITY'S STORMWATER |
| COLLECTION SYSTEM PER CITY ORDINANCE ARTICLE V, SEC. |
| 90-203 (A) WITHOUT PERMISSION FROM THE CITY. PLEASE |
| CONTACT MANNY GONZALEZ IN THE CITY OF WEST PALM BEACH |
| ENGINEERING DEPARTMENT AT 561- 494-1040 FOR FURTHER |
| DIRECTION ON THIS ISSUE. 2ND REQUEST. |
| 6) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW |
| PREVENTER. |
| 7) THE PLANS SHALL BE DIGITALLY SIGNED AND SEALED AS |
| REQD. PER FL. ADMIN. CODE RULE 61G15-23.004, |
| 61G15-23.005. 2ND REQUEST. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |
| |