Plan Review Notes
Plan Review Notes For Permit 20040725
Permit Number 20040725
Review Stop P
Sequence Number 2
Notes
Date Text
2020-05-14 16:46:09PLUMBING 1ST REVIEW DENIED**20040725
  
 1) SHT. P0.1 NOTE # 13 CALLS OUT ALL HOT WATER PIPING
 TO HAVE 1? WALL INSULATION. WHILE THIS IS CORRECT BUT
 ONLY UP TO 1 ?" PIPING. BEING YOUR PLAN SHOW SOME 1 ?"
 HOT WATER PIPE THAT WILL REQUIRED 1.5? THICK INSULATION
 THE NOTE COULD BE MISS LEADING. PLEASE CORRECT SHOW
 TABLE FBC-ENERGY C 403.2.10.
  
 2) PROVIDE SIZING AND HOW THIS GREASE TRAP IS SIZED FOR
 THE CURRENT KITCHEN USE. PLEASE PROVIDE HOW YOU SIZED
 BASE ON PDI G101 OR 64E-6
  
 3) PLEASE SHOWING TEMPERING ASSE1070 COMPLAINT. FBC-PLB
 607.1.2
  
 4) SHT P3.1 WATER ISOMETRIC IS MISSING THE REQUIRED
 SHUT OFF VALVES ON ALL DOWN FEED LINES. FBC-PLB 606.1
  
 5) THE SANITARY ISOMETRIC NEW FIXTURE ADDED DO NOT
 APPEAR TO BE PROPERLY VENTED. PLEASE CLARIFY WHICH
 VENTING METHOD IS YOUR DESIGN BASE ON FROM FBC-PLB
 CHAPTER 9. FBC 107.2.1
  
 TIM HUNT
  
 CITY OF WEST PALM BEACH
  
 (CAP GOVERNMENT)
  
 PLUMBING INSPECTOR
  
 PLUMBING PLAN EXAMINER [email protected]
  