Notes |
Date |
Text |
2020-05-14 16:46:09 | PLUMBING 1ST REVIEW DENIED**20040725 | | | | 1) SHT. P0.1 NOTE # 13 CALLS OUT ALL HOT WATER PIPING | | TO HAVE 1? WALL INSULATION. WHILE THIS IS CORRECT BUT | | ONLY UP TO 1 ?" PIPING. BEING YOUR PLAN SHOW SOME 1 ?" | | HOT WATER PIPE THAT WILL REQUIRED 1.5? THICK INSULATION | | THE NOTE COULD BE MISS LEADING. PLEASE CORRECT SHOW | | TABLE FBC-ENERGY C 403.2.10. | | | | 2) PROVIDE SIZING AND HOW THIS GREASE TRAP IS SIZED FOR | | THE CURRENT KITCHEN USE. PLEASE PROVIDE HOW YOU SIZED | | BASE ON PDI G101 OR 64E-6 | | | | 3) PLEASE SHOWING TEMPERING ASSE1070 COMPLAINT. FBC-PLB | | 607.1.2 | | | | 4) SHT P3.1 WATER ISOMETRIC IS MISSING THE REQUIRED | | SHUT OFF VALVES ON ALL DOWN FEED LINES. FBC-PLB 606.1 | | | | 5) THE SANITARY ISOMETRIC NEW FIXTURE ADDED DO NOT | | APPEAR TO BE PROPERLY VENTED. PLEASE CLARIFY WHICH | | VENTING METHOD IS YOUR DESIGN BASE ON FROM FBC-PLB | | CHAPTER 9. FBC 107.2.1 | | | | TIM HUNT | | | | CITY OF WEST PALM BEACH | | | | (CAP GOVERNMENT) | | | | PLUMBING INSPECTOR | | | | PLUMBING PLAN EXAMINER [email protected] | | |
|