2020-04-29 13:31:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20040725
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.2- IN THE KITCHEN HOOD MAKE-UP AIR UNIT
 SCHEDULE REMARKS, BOTH KSF-1 AND KSF-3 CALL FOR A NOTE
 12. THERE IS NO NOTE 12 IN THE REMARKS. PLEASE SHOW
 NOTE 12 IN THE REMARKS SECTION. FBC FS 107.2.1
  
 2) SHEET M1.2- VENTILATION NOTE; VENTILATION SHOULD BE
 BASED ON ASHRAE 62.1 ? 2013, NOT 2010 VERSION. FBC M
 403.3.1.1.2.3.2
  
 3) SHEET M1.2- PLEASE SHOW AN AIR BALANCE REPORT FOR
 THIS FACILITY. I DO NOT SEE THE HOOD EXHAUST RATES IN
 YOUR CHARTS. FBC M 508.1.2
  
 4) SHEET M1.2- TG-1 IN THE BATHROOM AREA IS USING THE
 RETURN SYMBOL, PLEASE CORRECT THIS AS YOU CANNOT USE
 THE BATHROOMS AS RETURN AIR. FBC M TABLE 403.3.1.1
 (NOTE G)
  
 5) SHEET M3.2- PLEASE SHOW A DETAIL DRAWING OF HOW
 KSF-2 IS COMPLYING WITH THE MAKEUP AIR TEMPERATURE
 REQUIREMENT. FBC M 508.1.1
  
 6) CAPTIVE AIRE HOODS SHEETS ARE NOT INCLUDED IN THIS
 PROJECT PACKAGE. SEPARATE PLAN REVIEWS AND PERMITS WILL
 BE REQUIRED FOR THE HOOD SYSTEMS ON THIS PROJECT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  