Plan Review Notes For Permit 20040725 |
Permit Number |
20040725 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-05-05 07:36:50 | GAS 1ST REVIEW**DENIED**20040725 | | | | | | 1) THE BTU?S DON?T ADD UP WHEN COMPARING THE GAS | | ISOMETRIC AND FIXTURE SCHEDULE ON SHT. P2.3. THE BTU | | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE | | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING | | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING | | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING | | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS | | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH | | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH | | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF | | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 | | | | | | TIM HUNT | | | | CITY OF WEST PALM BEACH | | | | (CAP GOVERNMENT) | | | | PLUMBING INSPECTOR | | | | PLUMBING PLAN EXAMINER [email protected] | | |
|