Plan Review Notes
Plan Review Notes For Permit 20040725
Permit Number 20040725
Review Stop G
Sequence Number 1
Notes
Date Text
2020-05-05 07:36:50GAS 1ST REVIEW**DENIED**20040725
  
  
 1) THE BTU?S DON?T ADD UP WHEN COMPARING THE GAS
 ISOMETRIC AND FIXTURE SCHEDULE ON SHT. P2.3. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3
  
  
 TIM HUNT
  
 CITY OF WEST PALM BEACH
  
 (CAP GOVERNMENT)
  
 PLUMBING INSPECTOR
  
 PLUMBING PLAN EXAMINER [email protected]
  