Plan Review Notes
Plan Review Notes For Permit 20040725
Permit Number 20040725
Review Stop E
Sequence Number 1
Notes
Date Text
2020-04-29 17:50:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved