Plan Review Notes
Plan Review Notes For Permit 20040725
Permit Number 20040725
Review Stop B
Sequence Number 1
Notes
Date Text
2020-05-04 13:09:03PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEITHER THE LIFE SAFETY SHEET A1.1 OR THE FLOOR PLAN
 SHEETS A2.1 & A2.2 SHOW ANY ACCESSIBILITY ELEMENTS FOR
 DINING, PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-EXISTING BUILDING SECTION 806.1 A BUILDING, OR
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY CODE. THE LIFE SAFETY SHEET DOES NOT SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE;
 1A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 1B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 1C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, BAR TOPS, HIGH TOPS AND OR OUTDOOR
 DINING AREAS.
  
 1D) 902.1 DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, BABY CHANGING AND
 OTHER TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS.
  
 1D) - (1)CLEAR FLOOR SPACE SHALL BE PROVIDED FOR A
 PARALLEL OR FORWARD APPROACH. FORWARD APPROACHES
 REQUIRE KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL
 BE PROVIDED OF THE 2017 FBC-ACCESSIBILITY CODE.
  
 1D) - (2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND, 2017
 FBC-ACCESSIBILITY CODE.
  
 2) THE PLANS DO NOT SHOW ACCESSIBILITY COMPLIANCE WITH
 THE REQUIRED COUNTER HEIGHT FOR THE BAR/POINT OF SALE
 LOCATED IN THE STUDENT ENGAGEMENT AREA. 2017
 ACCESSIBILITY CODE. SALES & SERVICE COUNTERS. 904.4.1.
 A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES LONG
 MINIMUM AND 36 INCHES HIGH MAXIMUM ABOVE THE FINISH
 FLOOR SHALL BE PROVIDED. A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 SHALL BE POSITIONED FOR A PARALLEL
 APPROACH ADJACENT TO THE 36 INCH MINIMUM LENGTH
 COUNTER.
  
 3) THE EXISTING BATHROOMS THAT SERVICE THE PRIMARY
 FUNCTION AREA FOR THIS PROJECT ARE REQUIRED TO COMPLY
 WITH THE 2017 FBC ACCESSIBILITY CODE UNLESS SHOWN TO BE
 A DISPROPORTIONATE COST. FBC ACCESSIBILITY 603 & 604
  
 4) THE PERMIT APPLICATION INDICATES THAT $4,700,000.00
 DOLLARS OF WORK IS TO BE ACCOMPLISHED UNDER THIS
 PERMIT. PLEASE PROVIDE A LETTER EITHER FROM THE
 CONTRACTOR OR DESIGNER OF RECORD ON THEIR LETTERHEAD
 WHERE UP TO 20 % OF THE CONTRACT VALUE IS GOING TO BE
 SPENT IN ACCESSIBLE UPGRADES TO THE PROJECT. IF ALL
 EXISTING CONDITIONS ARE COMPLETED (COMPLIED) BEFORE
 DISPROPORTIONATION COST IS MET A LETTER IS NOT
 REQUIRED. SHOW COMPLIANCE WITH THE:
 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 5) DOOR 103 ON SHEET A1.1 IS SHOWN SWINGING INWARD
 AGAINST THE DIRECTION OF EGRESS TRAVEL FROM THE
 BUILDING. FBC 1010.1.2.1
  
 6) UNDER CODE INFORMATION ON SHEET A01 THE PROJECT
 OCCUPANT LOAD IS SPECIFIED AS 48 PERSONS. THE
 CALCULATED OCCUPANT LOAD IS SPECIFIED AS 628 PERSONS ON
 SHEET A1.1. PLEASE CORRECT. FBC 107.2.1 & FBC
 1004.1.1.1
  
 7) SHEET A4.2 HAS AN EXTERIOR STAIR DETAIL #13 AND A
 STAIR SECTION #14. SUBMIT COMPLETE STRUCTURAL DETAILS
 FOR THESE STAIRS. FBC 107.2.1
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
  
  
  
  
  
  