2020-04-17 14:40:22PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, AT LOCATION #3, THE UPPER BEAM (2"X 8"X
 1/8") HAS A SPAN OF 17' 6", THE MAX. ALLOWABLE BEAM
 SPAN (PER PAGE 9 OF THE SHOP DRAWINGS) IS 11' 6". THE
 SITE SPECIFIC DRAWING DOES NOT CLEARLY APPROVE THIS
 SPAN.
 PLEASE PROVIDE A SIGNED/SEALED CLARIFICATION LETTER
 APPROVING THE BEAM SPAN WITH CALCULATIONS OR AN
 ALTERNATE METHOD.