Plan Review Notes For Permit 20040690 |
Permit Number |
20040690 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-04-17 14:40:22 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2.1, AT LOCATION #3, THE UPPER BEAM (2"X 8"X | | 1/8") HAS A SPAN OF 17' 6", THE MAX. ALLOWABLE BEAM | | SPAN (PER PAGE 9 OF THE SHOP DRAWINGS) IS 11' 6". THE | | SITE SPECIFIC DRAWING DOES NOT CLEARLY APPROVE THIS | | SPAN. | | PLEASE PROVIDE A SIGNED/SEALED CLARIFICATION LETTER | | APPROVING THE BEAM SPAN WITH CALCULATIONS OR AN | | ALTERNATE METHOD. |
|