2020-04-22 12:28:031ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20040643
 4/22/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS FA-01 & FA-19: THE DS DETECTORS ARE NOT SHOWN
 IN THE FACP SCHEDULE- SEE SECTION 907.3.1 FBC B.
  
 2) FA-02: THE BATTERY CABINETS MAY REQUIRE MECHANICAL
 VENTILATION PER SECTION 502.5 FBC M. SUBMIT A CUT SHEET
 FOR THE CABINETS AND THE BATTERIES. VRLA BATTERY
 CABINETS REQUIRE CONTINUOUS VENTILATION AT 1.0 CFM PER
 SQ. FT.- SECTION 502.5.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  