Plan Review Notes
Plan Review Notes For Permit 20040639
Permit Number 20040639
Review Stop E
Sequence Number 2
Notes
Date Text
2020-09-21 09:12:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) RISER SHOWS #6 COMING OFF 200A DISCONNECT TO THE
 PANEL.
  
 2) SMOKE ALARM AND CO DETECTOR TO CLOSE TO THE BATHROOM
 DOOR 3' UNLESS THERE IS NO OTER PLACE FOR IT. LOOKS
 LIKE IT COULD BE MOVED. MOVE IT INTO THE BEDROOM THERE
 IS NO DOOR R314.3 #4
  
 R314.3#4 SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN
 3 FEET (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING
 OF A BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS
 THIS WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED
 BY SECTION R314.3.
  
 3) KITCHEN COUNTER OUTLETS LOOK LIKE SOME ARE MISSING.
  
 THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER SPACE
 STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED SO
 THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS
 CODE IN SOME AREAS. PROVIDE CORRECTION. NEC
 210.52(C)(1); FBC RE3901.4