Plan Review Notes For Permit 20040603 |
Permit Number |
20040603 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-04-22 15:01:10 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT SIGNED AND SEALED ENGINEERING FOR DETERMINING | | THE OPENING PRESSURES. SPECIFY THE WINDSPEED, EXPOSURE | | CATEGORY AND MEAN ROOF HEIGHT OF THE BUILDING. FBC | | 107.2.1 THIS IS A FIVE STORY CONDOMINUM BUILDING, THE | | 2017 FBC RESIDENTIAL DOES NOT APPLY. THE RESIDENTIAL | | CODE ONLY APPLIES TWO ONE AND TWO FAMILY DWELLINGS AND | | TOWNHOUSES NO MORE THAN THREE STORIES. | | |
|