Plan Review Notes
Plan Review Notes For Permit 20040596
Permit Number 20040596
Review Stop P
Sequence Number 1
Notes
Date Text
2020-05-11 12:25:171) SHT. A3.2 - DETAIL D6 - SHOW THE HEIGHT OF THE SINK
 CABINET. MAXIMUM HEIGHT IS 34 INCHES ABOVE THE FINISH
 FLOOR TO THE HIGHER OF THE RIM OR COUNTER SURFACE.
 FBC-ACCESS. SEC.606.3.
 2) SHT. A1.1 - ADA MOUNTING HEIGHT DETAILS - GRAB BARS
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE,
 TO TO THE CENTERLINE AS SHOWN. FBC-ACCESS. SEC. 609.4.
 3) THE TOILET PAPER DISPENSER IS SHOWN AS 17-19 INCHES
 ABOVE THE FINISH FLOOR. THE OUTLET OF THE DISPENSER
 SHALL BE LOCATED 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISHED FLOOR.FBC-ACCESS. SEC.604.7
 4) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9
 INCHES TO THE CENTERLINE FROM THE FRONT OF THE BOWL.
 FBC-ACCESS. SEC. 604.7.
 5) THE WATER CLOSET IS SHOWN AS 18 INCHES MINIMUM FROM
 THE WALL. THE WATER CLOSET SHALL BE LOCATED 16-18
 INCHES FROM A SIDE WALL OR PARTITION. FBC-ACCESS.
 SEC.604.2.
 6) THE DETAILS SHOW VERTICAL GRAB BARS. THE GRAB BARS
 SHALL BE INSTALLED IN THE HORIZONTAL POSITION PER
 FBC-ACCESS. SEC. 609.4. THERE IS NO EXCEPTION IN THE
 COULD FOR GRAB BARS INSTALLED IN THE VERTICAL POSITION.
 7) SHT. A1.1 - SHOW THE DISTANCE UNDER THE LAVATORIES
 ON DETAIL E13. COMPLY WITH FBC-ACCESS. SEC. 306.
 8) SHOW THE LOCATION OF THE MOP SINK ON THE PLANS.
 TABLE 403.1.
 9) THE CONNECTION OF THE SUMP DRAIN TO THE BUILDING
 DRAIN SHALL BE LOCATED A MINIMUM OF 10 PIPE DIAMETERS
 AWAY FROM THE BASE OF THE STACK FOR SK-1 PER
 FBC-PLUMBING SEC. 712.3.5.
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SUMP
 FOR THE SINK AND FOR THE CONDENSATE PUMP. WPB AMEND. TO
 FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW