2020-04-22 16:30:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20040596
 4/22/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.1 NOTES 7 A. & B: THE PLANS SHOW FLEX DUCTS
 BUT THE SPECIFICATIONS FOR THE DUCTS WAS REMOVED FROM
 THE REVISED PLAN SHEET- SECTION 107.2.1 WPB.
  
 2) M2.1 NOTE #5: SHOW THE REQUIRED FIRE/SMOKE DAMPER AT
 THE PENETRATION OF THE O/A DUCT AT THE SHAFT- SECTION
 607.5.5 FBC M. CORRECT THE NOTE INDICATING O/A FOR
 RESTROOM EXHAUST- SECTION 107.2.1 WPB.
  
 3) M2.1: PROVIDE O/A TO THE HP-2 SYSTEM SUPPLYING
 OFFICES 734, 735, 736- SECTION 403.3 FBC M.
  
 4) M2.2 NOTE #4: SHOW THE REQUIRED FIRE/SMOKE DAMPER AT
 THE PENETRATION OF THE RESTROOM EXHAUST DUCT AT THE
 SHAFT- SECTION 607.5.5 FBC M.
  
 5) M2.2: PROVIDE A THERMOSTAT FOR THE NEW AHU-1 SYSTEM
 IN THE IT 715 ROOM- SECTION C403.2.4.1 FBC EC.
  
 6) M2.2: SHOW THE LOCATION OF THE CHASE FOR THE NEW
 REFRIGERANT LINES- SECTION 107.2.1 PROVIDE A NOTE TO
 INDICATE THE NEW SYSTEM AND REFRIGERANT LINES WILL
 INSTALLED PER MANUFACTURER'S SPECIFICATIONS- SECTION
 304.1 FBC M.
  
 7) M7.1: SHOW THE LOCATION OF THE NEW AC CONDENSER-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  