Plan Review Notes
Plan Review Notes For Permit 20040532
Permit Number 20040532
Review Stop P
Sequence Number 1
Notes
Date Text
2020-04-16 15:57:121ST REVIEW FBC-2017 PLUMBING
 PERMIT #20040532
 4/15/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 1, CORRECT GENERAL NOTE #1 TO INDICATE
 CONFORMANCE WITH THE FBC-17 RESIDENTIAL 6TH EDITION,
 AND THE REQUIREMENTS OF ANSI/APSP/ICC3; ANSI/APSP/ICC
 4; ANSI/ APSP/ICC 5; ANSI/APSP/ICC 6; AND ANSI/APSP/ICC
 7- SECTION 107.2.1 WPB & SECTION 4501.6.1 FBC RES.
  
 2) SHEET 1: CORRECT GENERAL NOTE #2 TO INDICATE PIPE
 TESTING TO BE IN ACCORDANCE WITH SECTION R4501.6.3.
  
 3) SHEET 1 & 2: PROVIDE THE WATER FLOW VELOCITIES OF
 THE POOL PRESSURE AND SUCTION PIPING, INCLUDING BRANCH
 SUCTION PIPING- SECTION R4501.6.3 FBC RES.
  
 4) SHEET 1 & 2: INDICATE THE MAKE AND MODEL OF THE
 UNBLOCKABLE DRAIN ASSEMBLY ON THE PLAN AND VERIFY IT IS
 ANSI/APSP/ICC 7 APPROVED PER SECTION R4501.6.6 FBC RES.
 SUBMIT A PRODUCT DATA SHEET AND INSTALLATION
 GUIDELINES- SECTION 107.2.1 WPB.
  
 5) SHEET 1, PROJECT SPECIFIC DETAILS: PROVIDE THE MAKES
 AND MODELS OF THE PUMP, FILTER, HEATER, AND THE
 CHLORINATOR- SECTION R4501.6.2 FBC RES.
  
 6) SHEET 2: PROVIDE A TOTAL DYNAMIC HEAD (TDH)
 CALCULATION FOR THE SYSTEM, AND INDICATE WHICH PUMP IS
 SELECTED ON THE PUMP CURVE (PUMP PERFORMANCE IN FEET OF
 HEAD AND GPM FLOW)- SECTION R4501.7.3 FBC RES.
  
 7) SHEET 1: INDICATE HOW WATER WILL BE SUPPLIED TO THE
 POOL. PLEASE NOTE THAT IF AN AUTO FILL IS INSTALLED A
 BACKFLOW DEVICE IS REQUIRED AT THE AUTO FILL, AND A
 REDUCED PRESSURE BACKFLOW DEVICE IS REQUIRED AT THE
 WATER METER PER THE CITY OF WEST PALM BEACH CROSS
 CONNECTION CONTROL MANUAL- R4501.9.
  
 8) SHEET 2: INDICATE A HYDROSTATIC RELIEF VALVE WILL BE
 INSTALLED AND PROVIDE A CROSS-SECTION DETAIL SHOWING
 THE DRAIN AND THE VALVE- R4501.21.4.
  
 9) SHEET 1: PLACE A NOTE INDICATING THE GAS-FIRED POOL
 HEATER WILL REQUIRE A SEPARATE PERMIT- SECTION 107.2.1
 WPB.
  
 10) SHEET 1: THE POOL SHALL BE EQUIPPED WITH A
 VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS-
 SECTION R403.10.3 FBC EC.
  
 11) SHEET 1, GENERAL NOTE $8: THERE IS NO INDICATION ON
 THE PLANS OR INFORMATION PROVIDED TO VERIFY AN APPROVED
 POOL BARRIER WILL BE INSTALLED- R4501.17 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  