Date |
Text |
2020-04-16 15:57:12 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT #20040532 |
| 4/15/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET 1, CORRECT GENERAL NOTE #1 TO INDICATE |
| CONFORMANCE WITH THE FBC-17 RESIDENTIAL 6TH EDITION, |
| AND THE REQUIREMENTS OF ANSI/APSP/ICC3; ANSI/APSP/ICC |
| 4; ANSI/ APSP/ICC 5; ANSI/APSP/ICC 6; AND ANSI/APSP/ICC |
| 7- SECTION 107.2.1 WPB & SECTION 4501.6.1 FBC RES. |
| |
| 2) SHEET 1: CORRECT GENERAL NOTE #2 TO INDICATE PIPE |
| TESTING TO BE IN ACCORDANCE WITH SECTION R4501.6.3. |
| |
| 3) SHEET 1 & 2: PROVIDE THE WATER FLOW VELOCITIES OF |
| THE POOL PRESSURE AND SUCTION PIPING, INCLUDING BRANCH |
| SUCTION PIPING- SECTION R4501.6.3 FBC RES. |
| |
| 4) SHEET 1 & 2: INDICATE THE MAKE AND MODEL OF THE |
| UNBLOCKABLE DRAIN ASSEMBLY ON THE PLAN AND VERIFY IT IS |
| ANSI/APSP/ICC 7 APPROVED PER SECTION R4501.6.6 FBC RES. |
| SUBMIT A PRODUCT DATA SHEET AND INSTALLATION |
| GUIDELINES- SECTION 107.2.1 WPB. |
| |
| 5) SHEET 1, PROJECT SPECIFIC DETAILS: PROVIDE THE MAKES |
| AND MODELS OF THE PUMP, FILTER, HEATER, AND THE |
| CHLORINATOR- SECTION R4501.6.2 FBC RES. |
| |
| 6) SHEET 2: PROVIDE A TOTAL DYNAMIC HEAD (TDH) |
| CALCULATION FOR THE SYSTEM, AND INDICATE WHICH PUMP IS |
| SELECTED ON THE PUMP CURVE (PUMP PERFORMANCE IN FEET OF |
| HEAD AND GPM FLOW)- SECTION R4501.7.3 FBC RES. |
| |
| 7) SHEET 1: INDICATE HOW WATER WILL BE SUPPLIED TO THE |
| POOL. PLEASE NOTE THAT IF AN AUTO FILL IS INSTALLED A |
| BACKFLOW DEVICE IS REQUIRED AT THE AUTO FILL, AND A |
| REDUCED PRESSURE BACKFLOW DEVICE IS REQUIRED AT THE |
| WATER METER PER THE CITY OF WEST PALM BEACH CROSS |
| CONNECTION CONTROL MANUAL- R4501.9. |
| |
| 8) SHEET 2: INDICATE A HYDROSTATIC RELIEF VALVE WILL BE |
| INSTALLED AND PROVIDE A CROSS-SECTION DETAIL SHOWING |
| THE DRAIN AND THE VALVE- R4501.21.4. |
| |
| 9) SHEET 1: PLACE A NOTE INDICATING THE GAS-FIRED POOL |
| HEATER WILL REQUIRE A SEPARATE PERMIT- SECTION 107.2.1 |
| WPB. |
| |
| 10) SHEET 1: THE POOL SHALL BE EQUIPPED WITH A |
| VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A |
| LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS- |
| SECTION R403.10.3 FBC EC. |
| |
| 11) SHEET 1, GENERAL NOTE $8: THERE IS NO INDICATION ON |
| THE PLANS OR INFORMATION PROVIDED TO VERIFY AN APPROVED |
| POOL BARRIER WILL BE INSTALLED- R4501.17 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |