2020-05-04 16:09:10 
 3RD REVIEW FBC-2017 FUEL GAS
 PERMIT #20040499
 5/4/202
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P003: THE 2" UG LINE IS UNDERSIZED FOR A GAS
 LOAD OF 7428- MBH AT 153 FT. TOTAL DEVELOPED LENGTH.
 USING TABLE 404.4(22) AS NOTED IN THE RISER DRAWING,
 THE 2" LINE WILL PROVIDE A MAXIMUM OF 7290- MBH AT 150'
 TOTAL LENGTH.
 2) AS REQUESTED IN THE PREVIOUS REVIEW, PROVIDE THE
 "PIPE LENGTH AND SIZE FOR LOW PRESSURE GAS TO
 GENERATOR".
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE RETORTS
 AND EXHAUST STACKS, AND PROVIDE AN EXHAUST STACK
 DIAGRAM THAT INDICATES THE TYPE AND SIZE OF STACK,
 TOTAL LENGTH OF RUN, CLEARANCE TO COMBUSTIBLES, EXHAUST
 DISCHARGE CLEARANCES, AND METHOD OF SUPPORT ABOVE THE
 ROOF- SECTION 606.1 FBC FG. PLEASE NOTE I DID NOT SEE
 ANY SPECS OR VENTING DIAGRAM IN THE APPROVED PLANS
 UNDER PERMIT #19070081.
 4) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE RETORTS
 AND SHOW HOW THE AIR IS BEING PROVIDED- SECTION 304.1
 FBC FG
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  