Date |
Text |
2020-05-04 16:09:10 | |
| 3RD REVIEW FBC-2017 FUEL GAS |
| PERMIT #20040499 |
| 5/4/202 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P003: THE 2" UG LINE IS UNDERSIZED FOR A GAS |
| LOAD OF 7428- MBH AT 153 FT. TOTAL DEVELOPED LENGTH. |
| USING TABLE 404.4(22) AS NOTED IN THE RISER DRAWING, |
| THE 2" LINE WILL PROVIDE A MAXIMUM OF 7290- MBH AT 150' |
| TOTAL LENGTH. |
| 2) AS REQUESTED IN THE PREVIOUS REVIEW, PROVIDE THE |
| "PIPE LENGTH AND SIZE FOR LOW PRESSURE GAS TO |
| GENERATOR". |
| 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE RETORTS |
| AND EXHAUST STACKS, AND PROVIDE AN EXHAUST STACK |
| DIAGRAM THAT INDICATES THE TYPE AND SIZE OF STACK, |
| TOTAL LENGTH OF RUN, CLEARANCE TO COMBUSTIBLES, EXHAUST |
| DISCHARGE CLEARANCES, AND METHOD OF SUPPORT ABOVE THE |
| ROOF- SECTION 606.1 FBC FG. PLEASE NOTE I DID NOT SEE |
| ANY SPECS OR VENTING DIAGRAM IN THE APPROVED PLANS |
| UNDER PERMIT #19070081. |
| 4) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE RETORTS |
| AND SHOW HOW THE AIR IS BEING PROVIDED- SECTION 304.1 |
| FBC FG |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |