2020-04-15 12:57:38 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT #20040431 |
| 4/25/20 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODESECTION |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE FLOOR PLAN DRAWING INDICATES THE SHOWER WALLS |
| ADJOIN WHAT MAY BE FIRE-RATED CORRIDOR AND TENANT |
| SEPARTION WALLS. INSTALLATION OF THE NEW SHOWER PAN |
| WHICH INVOLVES REMOVAL AND REPLACEMENT OF THE TILE AND |
| TILE BACKER ON THESE WALLS MAY REQUIRE A UL LISTED |
| ASSEMBLY REPAIR DETAIL- SECTION 107.2.1 WPB. |
| |
| 2) ) P1: INDICATE THE TYPE OF SHOWER VALVE TO BE |
| INSTALLED- SECTION 424.3 FBC P. PLEASE NOTE THAT |
| ACCEPTABLE VALVE TYPES ARE PRESSURE-BALANCE, |
| THERMOSTATIC-MIXING, OR COMBINATION |
| PRESSURE-BALANCED/THERMOSTATIC-MIXING CONFORMING TO THE |
| REQUIRERMENTS OF ASSE 1016/ASME A112.1016/CSA B125.16 |
| OR ASME A112.18.1/CSA B125.1 |
| |
| 3) P1: PROVIDE A SHOWER PAN AND LINER INSTALLATION |
| DETAIL- SEE SECTION 417.5.2 FBC P. PLEASE NOTE THAT |
| MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| INSTRUCTIONS FOR THE LINER SHALL BE ONSITE FOR |
| INSPECTION- SECTIONS 417.5.2.1 & 417.5.2.2 FBC P. |
| |
| 4) PLEASE NOTE THAT ALL PLANS SHALL BEAR THE SIGNATURE |
| OF THE CONTRACTOR WHO PREPARED THE DRAWINGS, OR THE |
| SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL WHO |
| PREPARED THE DRAWINGS- SECTIONS 107.2.1 AND 107.3.5 FBC |
| WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |