2020-04-14 05:34:261) SHT. P-5 - SHOW THE TYPE OF PIPE AND JOINTS TO BE
 INSTALLED FOR THE 3-INCH WATER LINE. WPB AMEND. TO FBC
 SEC. 107.2.1.
 2) A REDUCED PRESSURE BACKFLOW PREVENTION DEVICE IS
 REQUIRED ON THE 3-INCH WATER CONNECTION TO THE CHILLED
 WATER SYSTEM PER THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL.
 3) CLEARLY SHOW THE CONNECTION AND LOCATION POINT OF
 THE 3-INCH DOMESTIC WATER LINE TO THE CHILLED WATER
 SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 4) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW
 DEVICE THAT IS REQUIRED ON THE 3-INCH DOMESTIC WATER
 LINE CONNECTION.
  