2020-04-14 13:04:54 | REVIEWED BY JERRY SMITH. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20040371 101 N CLEMATIS ST 509 |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| 1. PER WPB FBC 107.2.1, REFERENCING APPLICATIONS ON THE |
| SUBMITTED SPEC HOME ADVII, INDICATE THE TYPES AND |
| QUANTITIES OF FIXTURES BEING SERVICED BY THE HA0118240 |
| UNIT. PROVIDE TOTAL DEMAND FOR UNIT AND INDICATE ON THE |
| SUBMITTAL WHICH INSERT WILL BE INCORPORATED IN THE |
| INSTALLATION. |
| 2. AS THE DOCUMENTS ARE NOT SIGNED AND SEALED BY A |
| PROFESSIONAL ENGINEER OR ARCHITECT, THE SUBMITTED |
| DOCUMENTS SHALL BEAR THE PRINTED NAME AND SIGNATURE OF |
| THE DESIGNER PER WPB FBC 107.2.1. |
| 3. PER WPB FBC 107.2.1, CONFIRM THAT REPLACEMENT WATER |
| HEATER IS TO BE INSTALLED IN SAME LOCATION AS THE |
| REPLACED STORAGE WATER HEATER AND THAT IT IS ACCESSIBLE |
| IN COMPLIANCE WITH FBC PL 501.4 OR PROVIDE PLAN SHOWING |
| LOCATIONS IF NOT THE SAME. |
| 4. UNIT WATTAGE IS 18 KW; TYPICALLY, A STORAGE TYPE |
| WATER HEATER IS NO MORE THAN 4.5 KW. PER WPB FBC |
| 107.2.1, AN ELECTRICAL PLAN AND PERMIT APPLICATION |
| SHALL BE SUBMITTED. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| REQUIRED BY FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-246-0882 MOBILE |
| |
| 20040371 101 N CLEMATIS ST 509 |
| |
| |