2020-04-14 13:04:54REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20040371 101 N CLEMATIS ST 509
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. PER WPB FBC 107.2.1, REFERENCING APPLICATIONS ON THE
 SUBMITTED SPEC HOME ADVII, INDICATE THE TYPES AND
 QUANTITIES OF FIXTURES BEING SERVICED BY THE HA0118240
 UNIT. PROVIDE TOTAL DEMAND FOR UNIT AND INDICATE ON THE
 SUBMITTAL WHICH INSERT WILL BE INCORPORATED IN THE
 INSTALLATION.
 2. AS THE DOCUMENTS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE SUBMITTED
 DOCUMENTS SHALL BEAR THE PRINTED NAME AND SIGNATURE OF
 THE DESIGNER PER WPB FBC 107.2.1.
 3. PER WPB FBC 107.2.1, CONFIRM THAT REPLACEMENT WATER
 HEATER IS TO BE INSTALLED IN SAME LOCATION AS THE
 REPLACED STORAGE WATER HEATER AND THAT IT IS ACCESSIBLE
 IN COMPLIANCE WITH FBC PL 501.4 OR PROVIDE PLAN SHOWING
 LOCATIONS IF NOT THE SAME.
 4. UNIT WATTAGE IS 18 KW; TYPICALLY, A STORAGE TYPE
 WATER HEATER IS NO MORE THAN 4.5 KW. PER WPB FBC
 107.2.1, AN ELECTRICAL PLAN AND PERMIT APPLICATION
 SHALL BE SUBMITTED.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  