2020-04-09 16:12:41MARKED UP PLANS TO SHOW THAT THE REQUIRED NEGATIVE
 PRESSURE FOR WINDOW C3 WHICH IS IN THE ONE STORY
 COTTAGE SHOULD BE -65.5 PSF WHICH IS OKAY FOR THE -70
 PSF LISTED IN THE PRODUCT APPROVAL NOA NO. 17-1011.25.