2020-05-14 14:36:33 | 2ND REVIEW FBC-2017 PLUMBING |
| PERMIT #20040366 |
| 5/14/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| COMMENT #2 FROM THE 1ST REVIEW PRINTED BELOW WAS NOT |
| COMPLETELY ADDRESSED. |
| |
| 2) PROVIDE A CONDENSATE DISPOSAL DIAGRAM SHOWING HOW |
| CONDENSATE FROM THE VENT FLUE, AND FROM THE BOILER |
| NEUTRALIZERS WILL BE DRAINED AND DISPOSED OF- SECTION |
| 107.2.1 WPB. SEE MECHANICAL COMMENT #1 FOR NEUTRALIZER |
| PRODUCT SUBMITTAL REQUIREMENT. |
| |
| THE REQUESTED DIAGRAM WAS NOT PROVIDED ON SHEET P-001. |
| AS STATED IN THE NARRATIVE RESPONSE BY THE EOR. SHEETS |
| P-001 & P-501: |
| A) PLEASE PROVIDE THE CONDENSATE DRAINAGE DIAGRAM |
| SHOWING THE DRAIN LINE RUN FROM THE VENT TO THE ACID |
| NEUTRALIZING TANK, AND THE WASTE LINE RUN FROM THE TANK |
| TO THE FLOOR DRAIN- SECTION 107.2.1 WPB. |
| B) P-501: SHOW THE CONDENSATE DRAIN LINE RUN TO THE |
| ACID TANK, AND THE WASTE LINE RUN TO THE FLOOR DRAIN ON |
| THE PLAN. |
| C) 2ND REQUEST TO SUBMIT SPECS FOR THE TANK. PLEASE |
| NOTE THAT SECTION 803.1 FBC P REQUIRES THAT AN |
| AUTOMATIC SUFFICIENT SUPPLY OF DILUTING WATER IS |
| REQUIRED SO AS TO MAKE THE CONTENTS NONINJURIOUS BEFORE |
| DISCHARGE INTO THE DRAINAGE SYSTEM. THE NATURE OF THE |
| CORROSIVE OR HARMFUL WASTE AND THE METHOD OF ITS |
| TREATMENT OR DILUTION SHALL BE APPROVED PRIOR TO |
| INSTALLATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| PLUMBING PLANS EXAMINER |