2020-05-14 16:23:27 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #20040366 |
| 5/14/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED |
| BASED ON THE RESUMBITTED PLANS AND THE NARRATIVE |
| RESPONSES BY THE ENGINEER OF RECORD, THE 1ST REVIEW |
| COMMENTS LISTED BELOW WILL BE MARKED AS PASSED OR |
| FAILED. |
| |
| 1) PASSED- DEFERRED SUBMITTAL ACCEPTED. PROVIDE A |
| SUBMITTAL PACKAGE THAT INCLUDES MANUFACTURER'S |
| SPECIFICATIONS AND INSTALLATION GUIDELINES FOR THE |
| BOILERS, PUMPS, EXPANSION TANK, CONTROL VALVES, RELIEF |
| VALVES, CHEMICAL FEEDER, CHEMICAL NEUTRALIZERS, VENT |
| FLUE AND VENT CAP, COMBUSTION AIR DUCTS, GAS AND |
| HYDRONIC PIPING, AND THE GAS REGULATORS AND SHUT OFF |
| VALVES- SECTION 107.2.1 WPB. REVIEW ALL REQUIRED |
| COMPLIANCES AND UL LISTINGS FOR THE PRODUCTS AS NOTED |
| ON THE SPECIFICATIONS SHEETS M101, 102, & 103 AS THEY |
| WILL BE CROSS CHECKED IN THE 2ND REVIEW. THE DESIGN |
| PROFESSIONAL OF RECORD SHALL PROVIDE APPROVAL STAMPS ON |
| EACH SUBMITTAL DOC, OR PROVIDE A STAMPED COVER PAGE |
| WITH AN INDEX LISTING ALL PRODUCT SUBMITTALS. |
| A) PASSED- DEFERRED SUBMITTAL. PLEASE NOTE THE GAS |
| BOILER SPECIFICATIONS SHALL INDICATE THAT THE UNITS ARE |
| LISTED IN ACCORDANCE WITH THE REQUIREMENTS OF ANSI |
| Z21.13 OR UL 795, AND DESIGNED AND CONSTRUCTED IN |
| ACCORDANCE WITH THE REQUIREMENTS OF ASME CSD-1 AND AS |
| APPLICABLE, THE ASME BOILER AND PRESSURE VESSEL CODE, |
| SECTIONS I, II, IV, V AND IX AND NFPA 85- SECTION 631.1 |
| FBC FG AND SECTION 1004.1 FBC M. |
| B) PASSED- DEFERRED SUBMITTAL. COMMISSIONING OF THE |
| BOILERS WILL REQUIRED AS NOTED UNDER ITEM 3.05 ON SHEET |
| M103 WHICH LISTS THE AIR AND WATER TESTING AND |
| BALANCING. COPIES OF THE TESTING REPORTS WILL BE |
| REQUIRED FOR FINAL MECHANICAL APPROVAL- SECTION C408.2 |
| FBC EC. |
| C) PASSED- DEFERRED SUBMITTAL. THE BOILER |
| SPECIFICATIONS SHALL INDICATE THAT THE UNITS HAVE BEEN |
| TESTED OR WILL BE TESTED TO A MAXIMUM LEVEL OF 50 PPM |
| OF CARBON MONOXIDE PER OSHA GUIDELINES- SECTION |
| 1004.2.1 FBC M. |
| |
| 2) FAILED. SHEET M401: PROVIDE THE EFFICIENCY RATINGS |
| OF THE BOILERS IN THE EQUIPMENT SCHEDULES- SEE TABLE |
| 404,2 FBC EC. |
| |
| 3) PASSED- DEFERRED SUBMITTAL. M401: VERIFY THE BOILER |
| SERVICE WATER SYSTEM WILL BE CAPABLE OF AUTOMATIC |
| TEMPERATURE RESET AND AUTOMATIC VARIABLE FLUID FLOW- |
| SEE SECTION C403.4.2.2 FBC EC. |
| |
| 4) PASSED- DEFERRED SUBMITTAL. M401: INDICATE THE |
| BOILER TURNDOWN RATIO AS REQUIRED BY SECTION C403.4.2.5 |
| FBC EC. |
| |
| 5) FAILED. WORKING CLEARANCES AT FRONTS, SIDES, REARS, |
| AND IN BETWEEN THE BOILERS NOT PROVIDED. PLEASE PROVIDE |
| FRONT AND TOP VIEW DRAWINGS OR DIAGRAMS OF THE BOILERS |
| THAT SHOW A) REQUIRED WORKING CLEARANCES AS NOTED IN |
| SECTIONS 1004.3 & 1004.3.1 FBC M. B) POTABLE WATER |
| SUPPLY PIPING CONNECTION AND LOCATION OF BACKFLOW |
| PREVENTERS AND SHUTOFF VALVES- SECTIONS 1005.1 & |
| 1005.2. C) WATER DISTRIBUTION PIPING AND CONNECTIONS |
| AND VALVE LOCATIONS- 1005.2 D) LOCATIONS AND |
| CONNECTIONS OF SAFETY RELIEF VALVES, PRESSURE RELIEF |
| VALVES, DISCHARGE PIPING AND DISCHARGE LOCATIONS- |
| SECTIONS 1006.2,1006.3, 1006.4, 1006.5, 1006.6, AND |
| 1006.7. E) LOCATION OF THE EXPANSION TANK- SECTION 1009 |
| FBC M. E) CONNECTION LOCATIONS OF THE GAS PIPING AND |
| REGULATOR, COMBUSTION AIR DUCTS, AND VENT DUCT- SECTION |
| 107.2.1 WPB. |
| |
| 6) PASSED. SHEET M501: SHOW THE LOCATION OF THE |
| REQUIRED FLOOR DRAIN FOR THE BOILERS- SECTION 1004.6 |
| FBC M. |
| |
| 7) PASSED. M501: SHOW THE GAS PIPING RUN INTO THE |
| BOILER ROOM- SECTION 107.2.1 WPB. |
| |
| 8) FAILED. GAS DRAWING DOES NOT SHOW TOTAL DEVELOPED |
| LENGTH OF THE SYSTEM, TYPE OF PIPINGS, TOTAL BTUH GAS |
| LOAD OF THE SYSTEM, CUT LENGTHS OF PIPINGS, DELIVERY |
| PRESSURES AT THE METER AND AT REGULATORS, GAS PIPE |
| SIZING TABLES, LOCATIONS OF DRIP LEGS, UNIONS. PROVIDE |
| A GAS ISOMETRIC DRAWING THAT SHOWS THE TYPE AND |
| DIAMETERS OF PIPING, THE MEASUREMENTS OF EACH CUT |
| LENGTH OF PIPE, THE TOTAL DEVELOPED LENGTH OF THE |
| PIPING RUN FROM THE POINT OF DELIVERY AT THE METER TO |
| THE MOST REMOTE OUTLET IN THE BUILDING AND TO THE |
| BOILERS; GAS DELIVERY PRESSURE OF THE SYSTEM AT THE |
| METER AND AT EACH STEPDOWN REGULATOR; LOCATIONS OF |
| REQUIRED SHUTOFF VALVES, AND THE BTUH LOADS OF THE NEW |
| BOILERS, AND ALL OTHER GAS-FIRED APPLIANCES AND |
| EQUIPMENT BEING SERVED BY THE SYSTEM- SECTIONS 402.2 |
| AND 402.3 FBC FG. PLEASE INDICATE WHICH PIPE SIZING |
| TABLES WERE USED IN THE DESIGN- SECTION 402.3. |
| A) FAILED. CONCERNING THE REGULATORS PLEASE REFER TO |
| SECTIONS 410.1, 410.2, & 410.3 FBC FG FOR LINE AND MP |
| REGULATOR INSTALLATION AND VENTING REQUIREMENTS. PLEASE |
| VERIFY SUBMITTALS ARE COMPLIANT AND SHOW ALL REGULATOR |
| AND SHUTOFF VALVES IN THE ISOMETRIC DRAWING, AND |
| REGULATOR VENT RUNS AND TERMINATION LOCATIONS WHERE |
| REQUIRED. |
| |
| 9) FAILED. A) THE VENT SIZING CALCULATIONS WERE NOT |
| PROVIDED- SECTION 501.14 FBC FG. B) SHEETS M-301 & |
| M-903 SHOW THE VENT ROOF FREESTANDING ABOVE THE ROOF. |
| SHEET M-501 INDICATES THE VENT TO BE IN A CHIMNEY |
| ENCLOSURE- WHICH IS IT? , IF THE VENT IS FREESTANDING, |
| SHOW THE ACTUAL HEIGHT OF THE VENT FLUE ABOVE THE ROOF |
| AND PROVIDE ENGINEERING FOR ANCHORING THE FLUE TO THE |
| ROOF STRUCTURE TO RESIST WIND PRESSURES- SECTION |
| 301.15- FBC M. C) INDICATE THE REQUIRED CLEARANCE FROM |
| THE VENT PENETRATION TO THE COMBUSTIBLE ROOFING |
| MATERIAL. D) PROVIDE A SUBMITTAL FOR THE VENT FLUES AND |
| COMBUSTION AIR DUCTS OR REQUEST DEFERRED. PROVIDE A |
| VENT FLUE DIAGRAM THAT SHOWS THE LENGTHS OF THE |
| CONNECTORS, HORIZONTAL AND VERTICAL RUN LENGTHS, TOTAL |
| RUN LENGTH OF THE SYSTEM, AND LOCATIONS OF OFFSETS, |
| FITTINGS ETC. PER THE NOTES ON SHEET M102 THE PROPOSED |
| SYSTEM REQUIRES ENGINEERED SIZING CALCULATIONS WHICH |
| SHALL ACCOMPANY THE VENTING DIAGRAM- SEE SECTION |
| 506.6.9.3 FBC FG. PLEASE INDICATE THE "VENTING |
| APPLIANCE CATEGORY" - I, II, III, OR IV THAT THE SYSTEM |
| IS BEING DESIGNED FOR, AND IF THE SYSTEM IS POSITIVE OR |
| NEGATIVE AND PRODUCES CONDENSATION- SEE SECTION 202 FBC |
| FG. CURRENTLY, A THOROUGH REVIEW OF THE SYSTEM CANNOT |
| BE ACCOMPLISHED WITHOUT THE DIAGRAM, AND ADDITIONAL |
| SPECIFICATIONS AND INFORMATION- SECTION 107.2.1 WPB. |
| PLEASE REFER BACK TO COMMENT #1 FOR SUBMITTAL |
| REQUIREMENTS AND REQUIRED UL LISTING AND LABELING. A) |
| M502: REFER TO SECTION 503.8 FBC FG AND SHOW THE |
| REQUIRED CLEARANCES FROM THE VENT FLUE TERMINATION TO |
| MECHANICAL AND GRAVITY AIR INTAKES OR ANY OPERABLE |
| OPENINGS INTO THE BUILDING. |
| |
| 10) PASSED. PROVIDE A COMBUSTION AIR DUCT DIAGRAM THAT |
| SHOWS THE LENGTHS OF THE CONNECTORS, HORIZONTAL AND |
| VERTICAL RUN LENGTHS, TOTAL RUN LENGTH OF THE SYSTEM, |
| AND LOCATIONS OF OFFSETS, FITTINGS ETC.- SECTION 304.1 |
| AND 304.11 FBC FG. CURRENTLY, A THOROUGH REVIEW OF THE |
| SYSTEM CANNOT BE ACCOMPLISHED WITHOUT THE DIAGRAM, AND |
| ADDITIONAL SPECIFICATIONS AND INFORMATION- SECTION |
| 107.2.1 WPB. PLEASE REFER BACK TO COMMENT #1 FOR |
| SUBMITTAL REQUIREMENTS AND REQUIRED UL LISTING AND |
| LABELING. |
| |
| 11) PASSED. M201: THE SCOPE OF WORK NOTES INDICATES |
| DEMOLITION OF AIR CONDITIONING UNITS, DUCTS, TERMINAL |
| BOXES ETC. HOWEVER THE DRAWINGS TO NOT SHOW ANY AC |
| DEMOLITION OR REWORK. PLEASE PROVIDE THE DRAWINGS- |
| SECTION 107.2.1 WPB. |
| |
| 12) PASSED. M401: PLEASE PLACE A NOTE THAT THE WELDER'S |
| CERTIFICATES AND WELDING PROCEDURES SHALL BE ONSITE AT |
| TIME OF INSPECTION- SECTION 107.2.1 WPB. |
| |
| 13) PASSED- SEE NOTE. PROVIDE UL LISTED FIRE STOPPING |
| ASSEMBLIES FOR THE PENETRATIONS OF THE VENT FLUE, AND |
| COMBUSTION AIR DUCTS THROUGH THE FIRE RATED WALLS AND |
| FLOOR CEILING ASSEMBLIES- SECTION 714 FBC B. NOTE: THE |
| PIPE PENETRATON FIRESTOPPING DETAIL ON M-903 DOES NOT |
| INDICATE IT IS A UL LISTED AND LABELED ASSEMBLY. |
| |
| 14) PASSED. INDICATE THE TYPE AND THICKNESSES OF THE |
| BOILER SERVICE WATER PIPING INSULATIONS AND PROVIDE A |
| PRODUCT SUBMITTAL- SEE TABLE C403.2.10 FBC EC. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |