2020-04-14 14:34:52 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT #20040366 |
| 4/14/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) REFER TO SECTION 608.16.2 FBC P AND PROVIDE A |
| PRODUCT SUBMITTAL FOR THE RPZ BACKFLOW PREVENTER. THE |
| POTABLE SUPPLY TO THE BOILER SHALL BE EQUIPPED WITH A |
| BACKFLOW PREVENTER WITH AN INTERMEDIATE ATMOSPHERIC |
| VENT COMPLYING WITH ASSE 1012 OR CSA B64.3. WHERE |
| CONDITIONING CHEMICALS ARE INTRODUCED INTO THE SYSTEM, |
| THE POTABLE WATER CONNECTION SHALL BE PROTECTED BY AN |
| AIR GAP OR A REDUCED PRESSURE PRINCIPLE BACKFLOW |
| PREVENTER, COMPLYING WITH ASSE 1013, CSA B64.4 OR AWWA |
| C511. |
| |
| 2) PROVIDE A CONDENSATE DISPOSAL DIAGRAM SHOWING HOW |
| CONDENSATE FROM THE VENT FLUE, AND FROM THE BOILER |
| NEUTRALIZERS WILL BE DRAINED AND DISPOSED OF- SECTION |
| 107.2.1 WPB. SEE MECHANICAL COMMENT #1 FOR NEUTRALIZER |
| PRODUCT SUBMITTAL REQUIREMENT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |