Plan Review Notes
Plan Review Notes For Permit 20040366
Permit Number 20040366
Review Stop P
Sequence Number 1
Notes
Date Text
2020-04-14 14:34:521ST REVIEW FBC-2017 PLUMBING
 PERMIT #20040366
 4/14/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 608.16.2 FBC P AND PROVIDE A
 PRODUCT SUBMITTAL FOR THE RPZ BACKFLOW PREVENTER. THE
 POTABLE SUPPLY TO THE BOILER SHALL BE EQUIPPED WITH A
 BACKFLOW PREVENTER WITH AN INTERMEDIATE ATMOSPHERIC
 VENT COMPLYING WITH ASSE 1012 OR CSA B64.3. WHERE
 CONDITIONING CHEMICALS ARE INTRODUCED INTO THE SYSTEM,
 THE POTABLE WATER CONNECTION SHALL BE PROTECTED BY AN
 AIR GAP OR A REDUCED PRESSURE PRINCIPLE BACKFLOW
 PREVENTER, COMPLYING WITH ASSE 1013, CSA B64.4 OR AWWA
 C511.
  
 2) PROVIDE A CONDENSATE DISPOSAL DIAGRAM SHOWING HOW
 CONDENSATE FROM THE VENT FLUE, AND FROM THE BOILER
 NEUTRALIZERS WILL BE DRAINED AND DISPOSED OF- SECTION
 107.2.1 WPB. SEE MECHANICAL COMMENT #1 FOR NEUTRALIZER
 PRODUCT SUBMITTAL REQUIREMENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  