Plan Review Notes
Plan Review Notes For Permit 20040366
Permit Number 20040366
Review Stop G
Sequence Number 1
Notes
Date Text
2020-04-14 13:21:131ST REVIEW FBC-2017 FUEL GAS
 PERMIT #20040366
 4/142020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS #1 & 2 LISTED BELOW ARE ALSO IN THE MECHANICAL
 REVIEW. PLEASE REFER TO MECHANICAL REVIEW COMMENTS FOR
 ADDITIONAL PLAN CORRECTIONS.
  
 1) PROVIDE A GAS ISOMETRIC DRAWING THAT SHOWS THE TYPE
 AND DIAMETERS OF PIPING, THE MEASUREMENTS OF EACH CUT
 LENGTH OF PIPE, THE TOTAL DEVELOPED LENGTH OF THE
 PIPING RUN FROM THE POINT OF DELIVERY AT THE METER TO
 THE MOST REMOTE OUTLET IN THE BUILDING AND TO THE
 BOILERS; GAS DELIVERY PRESSURE OF THE SYSTEM AT THE
 METER AND AT EACH STEPDOWN REGULATOR; LOCATIONS OF
 REQUIRED SHUTOFF VALVES, AND THE BTUH LOADS OF THE NEW
 BOILERS, AND ALL OTHER GAS-FIRED APPLIANCES AND
 EQUIPMENT BEING SERVED BY THE SYSTEM- SECTIONS 402.2
 AND 402.3 FBC FG. PLEASE INDICATE WHICH PIPE SIZING
 TABLES WERE USED IN THE DESIGN- SECTION 402.3.
 A) CONCERNING THE REGULATORS PLEASE REFER TO SECTIONS
 410.1, 410.2, & 410.3 FBC FG FOR LINE AND MP REGULATOR
 INSTALLATION AND VENTING REQUIREMENTS. PLEASE VERIFY
 SUBMITTALS ARE COMPLIANT AND SHOW ALL REGULATOR AND
 SHUTOFF VALVES IN THE ISOMETRIC DRAWING, AND REGULATOR
 VENT RUNS AND TERMINATION LOCATIONS WHERE REQUIRED.
  
 2) PROVIDE A SUBMITTAL PACKAGE THAT INCLUDES
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES FOR THE BOILERS, PUMPS, EXPANSION TANK,
 CONTROL VALVES, RELIEF VALVES, CHEMICAL FEEDER,
 CHEMICAL NEUTRALIZERS, VENT FLUE AND VENT CAP,
 COMBUSTION AIR DUCTS, GAS AND HYDRONIC PIPING, AND THE
 GAS REGULATORS AND SHUT OFF VALVES- SECTION 107.2.1
 WPB. REVIEW ALL REQUIRED COMPLIANCES AND UL LISTINGS
 FOR THE PRODUCTS AS NOTED ON THE SPECIFICATIONS SHEETS
 M101, 102, & 103 AS THEY WILL BE CROSS CHECKED IN THE
 2ND REVIEW. THE DESIGN PROFESSIONAL OF RECORD SHALL
 PROVIDE APPROVAL STAMPS ON EACH SUBMITTAL DOC, OR
 PROVIDE A STAMPED COVER PAGE WITH AN INDEX LISTING ALL
 PRODUCT SUBMITTALS.
  
 A) PLEASE NOTE THE GAS BOILER SPECIFICATIONS SHALL
 INDICATE THAT THE UNITS ARE LISTED IN ACCORDANCE WITH
 THE REQUIREMENTS OF ANSI Z21.13 OR UL 795, AND DESIGNED
 AND CONSTRUCTED IN ACCORDANCE WITH THE REQUIREMENTS OF
 ASME CSD-1 AND AS APPLICABLE, THE ASME BOILER AND
 PRESSURE VESSEL CODE, SECTIONS I, II, IV, V AND IX AND
 NFPA 85- SECTION 631.1 FBC FG AND SECTION 1004.1 FBC M
  
 3) REFER TO SECTIONS 406.4, THROUGH 406.6 FBC FG AND
 PROVIDE A GAS PIPING TESTING PROCEDURE ON THE PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  