2020-04-14 13:21:13 | 1ST REVIEW FBC-2017 FUEL GAS |
| PERMIT #20040366 |
| 4/142020 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| COMMENTS #1 & 2 LISTED BELOW ARE ALSO IN THE MECHANICAL |
| REVIEW. PLEASE REFER TO MECHANICAL REVIEW COMMENTS FOR |
| ADDITIONAL PLAN CORRECTIONS. |
| |
| 1) PROVIDE A GAS ISOMETRIC DRAWING THAT SHOWS THE TYPE |
| AND DIAMETERS OF PIPING, THE MEASUREMENTS OF EACH CUT |
| LENGTH OF PIPE, THE TOTAL DEVELOPED LENGTH OF THE |
| PIPING RUN FROM THE POINT OF DELIVERY AT THE METER TO |
| THE MOST REMOTE OUTLET IN THE BUILDING AND TO THE |
| BOILERS; GAS DELIVERY PRESSURE OF THE SYSTEM AT THE |
| METER AND AT EACH STEPDOWN REGULATOR; LOCATIONS OF |
| REQUIRED SHUTOFF VALVES, AND THE BTUH LOADS OF THE NEW |
| BOILERS, AND ALL OTHER GAS-FIRED APPLIANCES AND |
| EQUIPMENT BEING SERVED BY THE SYSTEM- SECTIONS 402.2 |
| AND 402.3 FBC FG. PLEASE INDICATE WHICH PIPE SIZING |
| TABLES WERE USED IN THE DESIGN- SECTION 402.3. |
| A) CONCERNING THE REGULATORS PLEASE REFER TO SECTIONS |
| 410.1, 410.2, & 410.3 FBC FG FOR LINE AND MP REGULATOR |
| INSTALLATION AND VENTING REQUIREMENTS. PLEASE VERIFY |
| SUBMITTALS ARE COMPLIANT AND SHOW ALL REGULATOR AND |
| SHUTOFF VALVES IN THE ISOMETRIC DRAWING, AND REGULATOR |
| VENT RUNS AND TERMINATION LOCATIONS WHERE REQUIRED. |
| |
| 2) PROVIDE A SUBMITTAL PACKAGE THAT INCLUDES |
| MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| GUIDELINES FOR THE BOILERS, PUMPS, EXPANSION TANK, |
| CONTROL VALVES, RELIEF VALVES, CHEMICAL FEEDER, |
| CHEMICAL NEUTRALIZERS, VENT FLUE AND VENT CAP, |
| COMBUSTION AIR DUCTS, GAS AND HYDRONIC PIPING, AND THE |
| GAS REGULATORS AND SHUT OFF VALVES- SECTION 107.2.1 |
| WPB. REVIEW ALL REQUIRED COMPLIANCES AND UL LISTINGS |
| FOR THE PRODUCTS AS NOTED ON THE SPECIFICATIONS SHEETS |
| M101, 102, & 103 AS THEY WILL BE CROSS CHECKED IN THE |
| 2ND REVIEW. THE DESIGN PROFESSIONAL OF RECORD SHALL |
| PROVIDE APPROVAL STAMPS ON EACH SUBMITTAL DOC, OR |
| PROVIDE A STAMPED COVER PAGE WITH AN INDEX LISTING ALL |
| PRODUCT SUBMITTALS. |
| |
| A) PLEASE NOTE THE GAS BOILER SPECIFICATIONS SHALL |
| INDICATE THAT THE UNITS ARE LISTED IN ACCORDANCE WITH |
| THE REQUIREMENTS OF ANSI Z21.13 OR UL 795, AND DESIGNED |
| AND CONSTRUCTED IN ACCORDANCE WITH THE REQUIREMENTS OF |
| ASME CSD-1 AND AS APPLICABLE, THE ASME BOILER AND |
| PRESSURE VESSEL CODE, SECTIONS I, II, IV, V AND IX AND |
| NFPA 85- SECTION 631.1 FBC FG AND SECTION 1004.1 FBC M |
| |
| 3) REFER TO SECTIONS 406.4, THROUGH 406.6 FBC FG AND |
| PROVIDE A GAS PIPING TESTING PROCEDURE ON THE PLAN. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |