2020-04-13 09:20:42 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE | | PRODUCT APPROVAL FOR THE FLAT DECK. | | 2) PLEASE PROVIDE SIGNED AND SEALED ADDITIONAL | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | ROOF ZONE 2 AND 3 THAT MAY HAVE HIGHER PRESSURES THAN | | THE MAXIMUM PRESSURE SHOWN FOR THE CHOSEN ROOFING | | SYSTEM IN THE PRODUCT APPROVAL PER PRODUCT APPROVAL | | "GENERAL LIMITATIONS" NOTE NUMBER 7. | | 3) SIGNED AND SEALED DOCUMENTS TO BE USED IN ELECTRONIC | | PLAN REVIEW NEED TO BE ELECTRONICALLY SIGNED BY THE | | ENGINEER OR ARCHITECT. | | |
|