2020-04-19 14:08:002017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040270
 ADD: 501 S FLAGLER DR. SUITE # 200
 CONT: ANDERSON MOORE
 TEL: 561-348-4805
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. APRIL 19TH/ 2020
 ACTION: DENIED
  
 1) SHEET ALS, THE LIFE SAFETY SHEET AND OTHER SHEETS
 EXAMPLE A1.1.1:
  
 1A) INDICATE ROOM 219 AS COPY AREA/ KITCHEN. WHEN THE
 WORDING KITCHEN IS USED IN THE COMMERCIAL CODES THE
 2017 FBC-B SECTION 904.2.2 WOULD REQUIRE COMMERCIAL
 HOOD AND EXHAUST SYSTEM. A BETTER WORDING FOR THE AREA
 IN QUESTION WOULD BE BREAK ROOM.
  
 1B) THERE IS A SECTION IN THE KITCHEN REFERENCING
 DETAIL 2/A4.0.2. THIS DETAIL SHOWS A SHELF ABOVE THE
 SINK WITH THE TOP OF THE SHELF AT A HEIGHT OF 4 FEET 9
 INCHES. THE ELECTRICAL SHEETS E0.1 & E3.1 SHOW 2
 ELECTRICAL CIRCUITS LABELED LA-12 & LA14 AND THE NOTE
 HT- TBD. I WILL TAKE THE NOTE TO MEAN HEIGHT TO BE
 DETERMINED. PLEASE NOTE IF THE DESIGNER OF RECORD FOR
 BOTH THE ARCHITECTURAL AND ELECTRICAL SHEETS IF IN THE
 FUTURE THESE OUTLETS ARE TO FEED A MICROWAVE APPLIANCE
 THE SHELF ITSELF IS HIGHER THAN ALLOWED BY THE 2017
 ACCESSIBILITY CODE SEE SECTIONS:
  
 308 REACH RANGES
 308.2 FORWARD REACH. / 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 1C) SHEET ALS UNDER THE HEADING CODE DATA DOES NOT
 INDICATE IF THERE ARE GANGED RESTROOMS (WITH ACCESSIBLE
 RESTROOMS) AND WATER FOUNTAINS (HIGH/ LOW)IN THE COMMON
 ELEMENTS OF THE CORRIDOR CORE OF THE BUILDING?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. THERE ARE
 2 ISSUES WITH THE RESTROOMS AS CONFIGURED SINCE WE NEED
 TO MEET BOTH THE REQUIREMENTS OF THE 2017 FBC-B SECTION
 2902.1 AND TABLE 2902.1 AND THE REQUIREMENTS FOUND
 UNDER THE 2017 FBC-ACCESSIBILITY CODE.
 IF THERE IS A DIFFERENCE BETWEEN CODES THE MOST
 STRINGENT THEN APPLIES. MISSING SERVICE SINK AND
 DRINKING FOUNTAIN.
 1C)(1) MUST MEET THE REQUIREMENTS FOUND IN TABLE 2902.1
 FOR BUSINESS OCCUPANCY FOR 39 0CCPUPANTS. SEPARATE
 FACILITIES WOULD BE REQUIRED BY FBC-B SECTION 2902.2,
 DOES NOT MEET ANY EXCEPTIONS.
  
 1C)(2) THE 2ND ISSUE IS UNDER THE 2017
 FBC-ACCESSIBILITY CODE 213.2 WHERE TOILET ROOMS ARE
 PROVIDED EACH TOILET ROOM SHALL COMPLY WITH 603. IF ONE
 OF THE EXCEPTIONS DOES APPLY PLEASE STATE SO ON THE
 PLANS.
  
 1D) DRINKING FOUNTAINS MUST COMPLY WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTION 211.2 MINIMUM NUMBER. NO
 FEWER THAN 2 DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
  
 2) SHEET A3.0.1. RESTROOM # 216 HAS A WALL MEASUREMENT
 OF 11 FEET 8 INCHES WHEN MEASURING THE DOOR THE DOOR
 MEASURES OUT TO BE APPROXIMATELY 4 FEET 5 INCHES. THERE
 IS A DISCREPANCY IN MEASUREMENTS FOR 11 FEET 8 INCHES?
 DISCREPANCY IN PLANS, 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED. WITH THE MEASUREMENT OF THE WALL AT 11
 FEET 8 INCHES THE DOOR SWING SHOULD CLEAR THE REQUIRED
 CLEAR FLOOR SPACE. ALSO YOU CAN SHOW COMPLIANCE WITH
 603.2.3 EX. # 2.
  
 3) SHEET A3.0.1.NEITHER OF THE RESTROOMS SHOW A
 COMPLIANT MIRROR. MIRRORS. 2017 FBC-ACCESSIBILITY CODE
 603.3 MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 4) SHEET A3.0.1. ACCESSIBLE LAVATORY. DETAIL # 6 NEEDS
 TO SHOW COMPLIANCE WITH:
  
 4A) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4B) 2017 FBC-ACCESSIBILITY CODE 606.4 FAUCETS. CONTROLS
 FOR FAUCETS SHALL COMPLY WITH 309. HAND-OPERATED
 METERING FAUCETS SHALL REMAIN OPEN FOR 10 SECONDS
 MINIMUM.
  
 4C) 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND
 SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES
 AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER LAVATORIES AND SINKS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717 / FAX: 561-805-6676
 E-MAIL: [email protected]
  