2020-04-19 14:08:00 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20040270 |
| ADD: 501 S FLAGLER DR. SUITE # 200 |
| CONT: ANDERSON MOORE |
| TEL: 561-348-4805 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SUN. APRIL 19TH/ 2020 |
| ACTION: DENIED |
| |
| 1) SHEET ALS, THE LIFE SAFETY SHEET AND OTHER SHEETS |
| EXAMPLE A1.1.1: |
| |
| 1A) INDICATE ROOM 219 AS COPY AREA/ KITCHEN. WHEN THE |
| WORDING KITCHEN IS USED IN THE COMMERCIAL CODES THE |
| 2017 FBC-B SECTION 904.2.2 WOULD REQUIRE COMMERCIAL |
| HOOD AND EXHAUST SYSTEM. A BETTER WORDING FOR THE AREA |
| IN QUESTION WOULD BE BREAK ROOM. |
| |
| 1B) THERE IS A SECTION IN THE KITCHEN REFERENCING |
| DETAIL 2/A4.0.2. THIS DETAIL SHOWS A SHELF ABOVE THE |
| SINK WITH THE TOP OF THE SHELF AT A HEIGHT OF 4 FEET 9 |
| INCHES. THE ELECTRICAL SHEETS E0.1 & E3.1 SHOW 2 |
| ELECTRICAL CIRCUITS LABELED LA-12 & LA14 AND THE NOTE |
| HT- TBD. I WILL TAKE THE NOTE TO MEAN HEIGHT TO BE |
| DETERMINED. PLEASE NOTE IF THE DESIGNER OF RECORD FOR |
| BOTH THE ARCHITECTURAL AND ELECTRICAL SHEETS IF IN THE |
| FUTURE THESE OUTLETS ARE TO FEED A MICROWAVE APPLIANCE |
| THE SHELF ITSELF IS HIGHER THAN ALLOWED BY THE 2017 |
| ACCESSIBILITY CODE SEE SECTIONS: |
| |
| 308 REACH RANGES |
| 308.2 FORWARD REACH. / 308.2.1 UNOBSTRUCTED/ 308.2.2 |
| OBSTRUCTED HIGH REACH. |
| 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| OBSTRUCTED HIGH REACH. |
| |
| 309 OPERABLE PARTS |
| 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE |
| OR MORE OF THE REACH RANGES SPECIFIED IN 308. |
| 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH |
| ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, |
| PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED |
| TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM. |
| |
| 1C) SHEET ALS UNDER THE HEADING CODE DATA DOES NOT |
| INDICATE IF THERE ARE GANGED RESTROOMS (WITH ACCESSIBLE |
| RESTROOMS) AND WATER FOUNTAINS (HIGH/ LOW)IN THE COMMON |
| ELEMENTS OF THE CORRIDOR CORE OF THE BUILDING? |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. THERE ARE |
| 2 ISSUES WITH THE RESTROOMS AS CONFIGURED SINCE WE NEED |
| TO MEET BOTH THE REQUIREMENTS OF THE 2017 FBC-B SECTION |
| 2902.1 AND TABLE 2902.1 AND THE REQUIREMENTS FOUND |
| UNDER THE 2017 FBC-ACCESSIBILITY CODE. |
| IF THERE IS A DIFFERENCE BETWEEN CODES THE MOST |
| STRINGENT THEN APPLIES. MISSING SERVICE SINK AND |
| DRINKING FOUNTAIN. |
| 1C)(1) MUST MEET THE REQUIREMENTS FOUND IN TABLE 2902.1 |
| FOR BUSINESS OCCUPANCY FOR 39 0CCPUPANTS. SEPARATE |
| FACILITIES WOULD BE REQUIRED BY FBC-B SECTION 2902.2, |
| DOES NOT MEET ANY EXCEPTIONS. |
| |
| 1C)(2) THE 2ND ISSUE IS UNDER THE 2017 |
| FBC-ACCESSIBILITY CODE 213.2 WHERE TOILET ROOMS ARE |
| PROVIDED EACH TOILET ROOM SHALL COMPLY WITH 603. IF ONE |
| OF THE EXCEPTIONS DOES APPLY PLEASE STATE SO ON THE |
| PLANS. |
| |
| 1D) DRINKING FOUNTAINS MUST COMPLY WITH THE 2017 |
| FBC-ACCESSIBILITY CODE SECTION 211.2 MINIMUM NUMBER. NO |
| FEWER THAN 2 DRINKING FOUNTAINS SHALL BE PROVIDED. ONE |
| DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 |
| AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. |
| |
| 2) SHEET A3.0.1. RESTROOM # 216 HAS A WALL MEASUREMENT |
| OF 11 FEET 8 INCHES WHEN MEASURING THE DOOR THE DOOR |
| MEASURES OUT TO BE APPROXIMATELY 4 FEET 5 INCHES. THERE |
| IS A DISCREPANCY IN MEASUREMENTS FOR 11 FEET 8 INCHES? |
| DISCREPANCY IN PLANS, 107.2.1.2 ADDITIONAL INFORMATION |
| IS REQUIRED. WITH THE MEASUREMENT OF THE WALL AT 11 |
| FEET 8 INCHES THE DOOR SWING SHOULD CLEAR THE REQUIRED |
| CLEAR FLOOR SPACE. ALSO YOU CAN SHOW COMPLIANCE WITH |
| 603.2.3 EX. # 2. |
| |
| 3) SHEET A3.0.1.NEITHER OF THE RESTROOMS SHOW A |
| COMPLIANT MIRROR. MIRRORS. 2017 FBC-ACCESSIBILITY CODE |
| 603.3 MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR |
| COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE |
| FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 4) SHEET A3.0.1. ACCESSIBLE LAVATORY. DETAIL # 6 NEEDS |
| TO SHOW COMPLIANCE WITH: |
| |
| 4A) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 4B) 2017 FBC-ACCESSIBILITY CODE 606.4 FAUCETS. CONTROLS |
| FOR FAUCETS SHALL COMPLY WITH 309. HAND-OPERATED |
| METERING FAUCETS SHALL REMAIN OPEN FOR 10 SECONDS |
| MINIMUM. |
| |
| 4C) 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND |
| SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES |
| AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR |
| ABRASIVE SURFACES UNDER LAVATORIES AND SINKS. |
| |
| 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |