Plan Review Notes
Plan Review Notes For Permit 20040218
Permit Number 20040218
Review Stop G
Sequence Number 1
Notes
Date Text
2020-04-30 10:03:081) THE POOL HEATER SHALL COMPLY WITH 2017 FBC-ENERGY
 SEC. R403.10.4. THE SUBMITTED HEATER SPECS DO NOT SHOW
 COMPLIANCE.
 R403.10.4GAS- AND OIL-FIRED POOL AND SPA HEATERS.
 ALL GAS- AND OIL-FIRED POOL AND SPA HEATERS SHALL HAVE
 A MINIMUM THERMAL EFFICIENCY OF 82 PERCENT FOR HEATERS
 MANUFACTURED ON OR AFTER APRIL 16, 2013, WHEN TESTED IN
 ACCORDANCE WITH ANSI Z 21.56. POOL HEATERS FIRED BY
 NATURAL OR LP GAS SHALL NOT HAVE CONTINUOUSLY BURNING
 PILOT LIGHTS.
 2) SINCE THE SYSTEM IS BEING INCREASED TO A 2 PSI
 SYSTEM, SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE REGULATORS.
 3) CITY RECORDS SHOW AN EXISTING GAS SYSTEM AT THIS
 PROPERTY. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST
 BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
 4) INDICATE ON THE PLAN WHICH SIZING TABLE FROM THE GAS
 CODE IS BEING USED FOR THE 2 PSI SYSTEM.
 5) REGULATORS WILL BE REQUIRED ON THE EXISTING
 APPLIANCES OR ONE REQULATOR ON THE EXISTING LINE GOING
 INTO THE HOUSE. SHOW ON THE PLANS.
 6) INDICATE TYPE OF PIPE BEING INSTALLED UNDERGROUND.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW