Date |
Text |
2020-04-30 10:03:08 | 1) THE POOL HEATER SHALL COMPLY WITH 2017 FBC-ENERGY |
| SEC. R403.10.4. THE SUBMITTED HEATER SPECS DO NOT SHOW |
| COMPLIANCE. |
| R403.10.4GAS- AND OIL-FIRED POOL AND SPA HEATERS. |
| ALL GAS- AND OIL-FIRED POOL AND SPA HEATERS SHALL HAVE |
| A MINIMUM THERMAL EFFICIENCY OF 82 PERCENT FOR HEATERS |
| MANUFACTURED ON OR AFTER APRIL 16, 2013, WHEN TESTED IN |
| ACCORDANCE WITH ANSI Z 21.56. POOL HEATERS FIRED BY |
| NATURAL OR LP GAS SHALL NOT HAVE CONTINUOUSLY BURNING |
| PILOT LIGHTS. |
| 2) SINCE THE SYSTEM IS BEING INCREASED TO A 2 PSI |
| SYSTEM, SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE REGULATORS. |
| 3) CITY RECORDS SHOW AN EXISTING GAS SYSTEM AT THIS |
| PROPERTY. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST |
| BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO |
| ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF |
| UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO |
| ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING |
| RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, |
| 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, |
| G2413.2, G2413.3. |
| 4) INDICATE ON THE PLAN WHICH SIZING TABLE FROM THE GAS |
| CODE IS BEING USED FOR THE 2 PSI SYSTEM. |
| 5) REGULATORS WILL BE REQUIRED ON THE EXISTING |
| APPLIANCES OR ONE REQULATOR ON THE EXISTING LINE GOING |
| INTO THE HOUSE. SHOW ON THE PLANS. |
| 6) INDICATE TYPE OF PIPE BEING INSTALLED UNDERGROUND. |
| |