Plan Review Notes
Plan Review Notes For Permit 20040178
Permit Number 20040178
Review Stop B
Sequence Number 2
Notes
Date Text
2020-04-09 11:21:47RESIDENTIAL (R3) RE-ROOF SECOND REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ROOF TILE FL7473-R8 SUBMITTED: CLEARLY MARK ADHESIVE
 PADDY SIZE AS REQUIRED BY CITY POLICY FOR ALL ROOFING
 PERMITS TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES
 OF SEC R301.2.1 FBC-RESIDENTIAL.
 NOTE: KEEP IN MIND THAT THIS PROPERTY IS LOCATED IN
 EXPOSURE "D".
  
 RESPONSE:
 STACEY SENT E-MAIL ON 04/07/2020 STATING THAT USING
 SCREWS INSTEAD OF ADHESIVE. TOLD HER THAT NEED TO
 SPECIFY SIZE AND NUMBER OF SCREWS TO VERIFY UPLIFT.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 2-OK.
  
 3- OK
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  