2020-04-06 12:38:11 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- ROOF TILE FL7473-R8 SUBMITTED: CLEARLY MARK ADHESIVE |
| PADDY SIZE AS REQUIRED BY CITY POLICY FOR ALL ROOFING |
| PERMITS TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES |
| OF SEC R301.2.1 FBC-RESIDENTIAL. |
| NOTE: KEEP IN MIND THAT THIS PROPERTY IS LOCATED IN |
| EXPOSURE "D". |
| |
| 2- ROOF TILE ADHESIVE FL6332-R8 SUBMITTED: CLEARLY MARK |
| ADHESIVE PADDY SIZE IN TABLE 1 (FIELD TILE) AND TABLE 2 |
| (HIP & RIDGE TILES) AS REQUIRED BY CITY POLICY FOR ALL |
| ROOFING PERMITS TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC R301.2.1 FBC-RESIDENTIAL. |
| NOTE: KEEP IN MIND THAT THIS PROPERTY IS LOCATED IN |
| EXPOSURE "D". |
| |
| 3- ROOF TILE UNDERLAYMENT FL14317-R9 SUBMITTED. CLEARLY |
| IDENTIFY WHICH UNDERLAYMENT IS GOING TO BE USED. AND, |
| CLEARLY SPECIFY/MARK WHICH APPROVED SYSTEM FROM SEC. |
| 5.6 OF FLORIDA PRODUCT APPROVAL SUBMITTED IS GOING TO |
| BE INSTALLED. |
| NEED THIS TO VERIFY THE WIND RESISTANCE REQUIRED BY |
| SEC. R301.2.1 FBC-RESIDENTIAL FOR UNDERLAYMENTS SYSTEMS |
| IN ADHESIVE-SET-TILE APPLICATIONS. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |