2021-04-12 16:58:07 | 04/12/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE SUBMIT SECONDARY (EMERGENCY) ROOF DRAIN |
| SYSTEMS THAT IS SIZED IN ACCORDANCE WITH SECTION 1106 |
| BASED ON THE RAINFALL RATE FOR WHICH THE PRIMARY SYSTEM |
| IS SIZED. SCUPPERS SHALL BE SIZED TO PREVENT THE DEPTH |
| OF PONDING WATER FROM EXCEEDING THAT FOR WHICH THE ROOF |
| WAS DESIGNED AS DETERMINED BY SECTION 1101.7. SCUPPERS |
| SHALL HAVE AN OPENING DIMENSION OF NOT LESS THAN 4 |
| INCHES (102 MM) IN HEIGHT AND HAVE AN OPENING WIDTH |
| EQUAL TO THE CIRCUMFERENCE OF THE ROOF DRAIN REQUIRED |
| FOR THE AREA SERVED PER THE 2020 FBC SECTION 1108.3 |
| SIZING OF SECONDARY DRAINS. |
| |
| 2. PLEASE REFER TO BUILDING COMMENTS AS WELL. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |