2021-04-12 16:58:0704/12/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT SECONDARY (EMERGENCY) ROOF DRAIN
 SYSTEMS THAT IS SIZED IN ACCORDANCE WITH SECTION 1106
 BASED ON THE RAINFALL RATE FOR WHICH THE PRIMARY SYSTEM
 IS SIZED. SCUPPERS SHALL BE SIZED TO PREVENT THE DEPTH
 OF PONDING WATER FROM EXCEEDING THAT FOR WHICH THE ROOF
 WAS DESIGNED AS DETERMINED BY SECTION 1101.7. SCUPPERS
 SHALL HAVE AN OPENING DIMENSION OF NOT LESS THAN 4
 INCHES (102 MM) IN HEIGHT AND HAVE AN OPENING WIDTH
 EQUAL TO THE CIRCUMFERENCE OF THE ROOF DRAIN REQUIRED
 FOR THE AREA SERVED PER THE 2020 FBC SECTION 1108.3
 SIZING OF SECONDARY DRAINS.
  
 2. PLEASE REFER TO BUILDING COMMENTS AS WELL.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  