Plan Review Notes
Plan Review Notes For Permit 20040149
Permit Number 20040149
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-12 09:12:03PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE REVISION APPLICATION STATES THAT THE NUMBER OF
 OVERFLOW SCUPPERS IS TO BE REDUCED FROM (4) FOUR TO (3)
 THREE. THE PLAN SHEET THAT WAS SUBMITTED ONLY SHOWS THE
 SCUPPER DETAILS. IN ORDER TO SHOW COMPLIANCE WITH THE
 FBC YOU WILL NEED TO SUBMIT THE ROOF PLANS THAT SHOW
 THE LOCATIONS OF THE OVERFLOW SCUPPERS AND SHOW THAT
 THEY CAN PROVIDE THE REQUIRED ROOF DRAINAGE. INDICATE
 THE LOCATION OF THE (1) ONE THAT IS BEING ELIMINATED
 AND THE LOCATIONS OF THE (3) THAT WILL REMAIN. FBC
 AMENDMENTS 107.2.1
  
 2) SUBMIT CALCULATIONS TO SHOW THAT THE (3) THREE
 REMAINING OVERFLOW SCUPPERS WILL PROVIDE THE REQUIRED
 AMOUNT OF ROOF DRAINAGE. FBC 1503.4
  
  