Plan Review Notes For Permit 20040149 |
Permit Number |
20040149 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-04-12 09:12:03 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | REVISION DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE REVISION APPLICATION STATES THAT THE NUMBER OF | | OVERFLOW SCUPPERS IS TO BE REDUCED FROM (4) FOUR TO (3) | | THREE. THE PLAN SHEET THAT WAS SUBMITTED ONLY SHOWS THE | | SCUPPER DETAILS. IN ORDER TO SHOW COMPLIANCE WITH THE | | FBC YOU WILL NEED TO SUBMIT THE ROOF PLANS THAT SHOW | | THE LOCATIONS OF THE OVERFLOW SCUPPERS AND SHOW THAT | | THEY CAN PROVIDE THE REQUIRED ROOF DRAINAGE. INDICATE | | THE LOCATION OF THE (1) ONE THAT IS BEING ELIMINATED | | AND THE LOCATIONS OF THE (3) THAT WILL REMAIN. FBC | | AMENDMENTS 107.2.1 | | | | 2) SUBMIT CALCULATIONS TO SHOW THAT THE (3) THREE | | REMAINING OVERFLOW SCUPPERS WILL PROVIDE THE REQUIRED | | AMOUNT OF ROOF DRAINAGE. FBC 1503.4 | | | | |
|