2020-04-15 10:00:47CHANGE OF OCCUPANCY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE OCCUPANCY CLASSIFICATION PER FBC
 CHAPTER 3.
 2) PLEASE PROVIDE A LIFE SAFETY PLAN SHOWING MEANS OF
 EGRESS FBC CHAPTER10, FIRE SPRINKLERS FBC 420.5, FIRE
 ALARMS AND SMOKE ALARMS FBC 420.6 ETC.
 3) PLEASE SHOW THE NUMBER OF OCCUPANTS.
 4) PLEASE SHOW THE FIRE RATING OF THE SEPARATION WALLS
 TO COMPLY WITH FBC 420.2
 5) PLEASE DESCRIBE THE USE FOR THE BUILDING - WHAT ARE
 THE OCCUPANTS THERE FOR?
  
 GROUP R-4 OCCUPANCIES SHALL MEET THE REQUIREMENTS FOR
 CONSTRUCTION AS DEFINED FOR GROUP R-3, EXCEPT AS
 OTHERWISE PROVIDED FOR IN THIS CODE OR SHALL COMPLY
 WITH THE FLORIDA BUILDING CODE, RESIDENTIAL PROVIDED
 THE BUILDING IS PROTECTED BY AN AUTOMATIC SPRINKLER
 SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.2.8.
  
 310.6.1CONDITION 1.
 THIS OCCUPANCY CONDITION SHALL INCLUDE BUILDINGS IN
 WHICH ALL PERSONS RECEIVING CUSTODIAL CARE, WITHOUT ANY
 ASSISTANCE, ARE CAPABLE OF RESPONDING TO AN EMERGENCY
 SITUATION TO COMPLETE BUILDING EVACUATION. 310.6.2
 CONDITION 2. THIS OCCUPANCY CONDITION SHALL INCLUDE
 BUILDINGS IN WHICH THERE ARE ANY PERSONS RECEIVING
 CUSTODIAL CARE WHO REQUIRE LIMITED VERBAL OR PHYSICAL
 ASSISTANCE WHILE RESPONDING TO AN EMERGENCY SITUATION
 TO COMPLETE BUILDING EVACUATION.
  
 310.6.2CONDITION 2.
 THIS OCCUPANCY CONDITION SHALL INCLUDE BUILDINGS IN
 WHICH THERE ARE ANY PERSONS RECEIVING CUSTODIAL CARE
 WHO REQUIRE LIMITED VERBAL OR PHYSICAL ASSISTANCE WHILE
 RESPONDING TO AN EMERGENCY SITUATION TO COMPLETE
 BUILDING EVACUATION.