2020-04-15 14:39:25 | GENERATOR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE PROVIDE A SITE PLAN SHOWING THE GENERATOR | | LOCATION AND THE 10 FOOT DISTANCE FROM OPENINGS INTO | | THE HOUSE PER FBC R303.5.1 | | 2) PLEASE PROVIDE SIGNED AND SEALED TIEDOWN AND | | FOUNDATION DETAILS FROM AN ARCHITECT OR ENGINEER TO | | COMPLY WITH THE WIND LOADS PER FBC R301.1 | | |
|